Siemens SIMATIC ET 200SP Manual page 37

Cpu 1512sp-1 pn 6es7512-1dk01-0ab0
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Interface hardware
Number of ports
Integrated switch
RJ45 (Ethernet)
BusAdapter (PROFINET)
Protocols
PROFINET IO controller
PROFINET IO device
SIMATIC communication
Open IE communication
Web server
Media redundancy
PROFINET IO controller
Services
CPU 1512SP-1 PN (6ES7512-1DK01-0AB0)
Manual, 09/2016, A5E33591411-AC
PG/OP communication
S7 routing
Isochronous mode
Open IE communication
IRT
MRP
MRPD
PROFIenergy
Prioritized startup
Number of connectable IO devices, max.
of these, IO devices with IRT, max.
Number of connectable IO devices for RT,
max.
of these, in a line topology, max.
Number of IO devices that can be activat-
ed/deactivated simultaneously, max.
Number of IO devices per tool, max.
Update times
Technical specifications
6ES7512-1DK01-0AB0
3; 1st integrated + 2nd via BusAdapter
Yes
Yes; X1 P3; opt. X1 P1 and X1 P2 via BusAdapt-
er BA 2xRJ45
Yes; usable BusAdapters: BA 2x RJ45, BA 2x
FC, BA 2x SCRJ, BA SCRJ / RJ45, BA SCRJ /
FC, BA 2x LC, BA LC / RJ45, BA LC / FC
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes; as MRP redundancy manager and/or MRP
client; max. number of devices in the ring: 50
Requirement: IRT
Yes
Yes; max. 32 PROFINET devices
128; a total of up to 512 distributed I/O devices
can be connected via AS-i, PROFIBUS or
PROFINET
64
128
128
8; in total over all interfaces
8
The minimum value of the update time also de-
pends on the communication allocation setting for
PROFINET IO, the number of IO devices and the
amount of configured user data
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents