TraceTek Leak DeTecTion MasTer MoDuLe insTaLLaTion insTrucTions
AppROVALS ANd cERTIfIcATIONS
TYPE NM
General Signaling Equipment
76LJ
WARNING:
Shock hazard. Shut off power before opening enclosure door.
THERMAL MANAGEMENT SOLUTIONS
TTDM-128
EN-TraceTekTTDM128-IM-H57341      03/13
GENERAL INfORMATION
Please read these instructions carefully and keep them in a safe
place (preferably close to the TTDM-128) for future reference.
These instructions must be followed carefully to ensure proper
operation.
The TTDM-128 Leak Detection Master Module has been designed
specifically for use with TraceTek sensing cables, point sensors,
sensor interface modules and relay modules. The TTDM-128 can
directly monitor up to 1500 m (5000 ft) of sensing cable, and large
networks of remote leak detection modules.
An external disconnect device and appropriate branch circuit
protection (no more than 20 amp rating) should be provided for
the TTDM-128. The disconnect device should be clearly marked
as such. Follow all national and local codes and regulations
applicable to the installation.
TOOLS REqUIREd
• Drill or hole punch for electrical conduit entries
• Phillips (cross-head) screwdriver
• Small flat-head screwdriver
INSTALLATION ITEMS (NOT SUppLIEd
• Wall fasteners for surface mounting (four screws)
STORAGE
Keep the module in a dry place prior to installation to avoid
possible damage to internal components.
pROdUcT INfORMATION
TTdM-128
115 Vac +15%, –20%; 50/60 Hz
230 Vac ±10%; 50/60 Hz
TTdM-128-24V
24 Vac +5%, –35%
power consumption
10 VA for TTDM-128
12 VA for TTDM-128-24 V
Installation categories
Overvoltage Category II, Pollution Degree 2
Built-in relays
Number: Three (Service, Leak, Fault)
Type:
Rating:
Storage temperature
–18°C to 60°C (0°F to 140°F)
Operating temperature
0°C to 50°C (32°F to 122°F)
Enclosure
NEMA 12; IP 54
)
24 Vdc ±20%
DPDT
5 A at 250 Vac/24 Vdc
1 / 6

Advertisement

loading

Summary of Contents for Pentair TraceTek TTDM-128

  • Page 1 TTDM-128 TraceTek Leak DeTecTion MasTer MoDuLe insTaLLaTion insTrucTions GENERAL INfORMATION Please read these instructions carefully and keep them in a safe place (preferably close to the TTDM-128) for future reference. These instructions must be followed carefully to ensure proper operation. The TTDM-128 Leak Detection Master Module has been designed specifically for use with TraceTek sensing cables, point sensors, sensor interface modules and relay modules.
  • Page 2                               LCD display Sensor Interface board Gland plate RS-485 TraceTek Network Plug & Socket LEDs with icons Motherboard Fault relay cable plug and socket Ribbon cable...
  • Page 3 Mounting the Enclosure Figure 3 300 mm Install the enclosure using the four screws in the prepunched 8 (11.81 in) 20 mm mm (5/16-inch) mounting holes with centers as shown in Figure 3. (0.79 in) 261 mm If plastic plugs are in the mounting holes, remove them. Make sure (10.26 in) the rubber elastomeric washers (provided in the shipping box) are aligned to seal around the mounting screws to maintain the NEMA...
  • Page 4 connect the alarm relays.  SERVICE RELAY LEAK RELAY  FAULT RELAY  The TTDM-128 has three relays, for service ck, leak bt, and fault bs. Each relay provides two Form-C relay contacts, and normally open and normally closed contacts are both provided. The relays are de-energized to indicate an alarm condition.
  • Page 5 connect the Sensing cable If the TTDM-128 will be used to monitor a sensor directly, follow prepare sensing cable. these instructions to connect the sensor to the TTDM-128. If the Ensure that the sensing cable has been installed and tested in ac- TTDM-128 is being used only as a network master, skip to Con- cordance with the instructions provided with the cable.
  • Page 6 Fax: +1.650.474.7215 thermal.info@pentair.com Pentair and TraceTek are owned by Pentair or its global affiliates. All other trademarks are the property of their respective owners. Pentair reserves the right to change specifications without prior notice. © 2003-2013 Pentair. PN P000000079 THERMAL MANAGEMENT SOLUTIONS EN-TraceTekTTDM128-IM-H57341      03/13...

This manual is also suitable for:

Tracetek ttdm-128-24v