Application 2 - Bosch Heatronic 4000 Applications Manual

Controls
Hide thumbs Also See for Heatronic 4000:
Table of Contents

Advertisement

1 2 | Bosch Heatronic 4000 Controls

3.4 Application 2

Description:
Single temperature system with two modulating condensing boilers
operated to provide heat for space heating and indirect DHW
loads. The boiler target temperature for the space heating load is
determined from outdoor temperature reset. Piping schematic is
reverse / return with bypass.
Essential Source (#) Settings:
ENABLE (1) = AUTO
BOSC BOILER (1) = YES
BOSC MODL (1) = "SB-Series"
ENABLE (2) = AUTO
Essential System Settings:
APP MODE = RSET
PUMP 1 = AUTO
PUMP 2 = OFF
IDHW MODE = ON
Application 2 Piping:
LEGEND:
S1 = Outdoor Sensor
S2 = Primary Supply Sensor
S3 = Primary Return Sensor
S4 = DHW Sensor
S6
SB Series
DISCLAIMER: Application drawings in this manual are conceptual only and do not purport to address all design, installation, code, or safety considerations. The diagrams in this manual are for reference use by code officials, designers and
licensed installers. It is expected that installers have adequate knowledge of national and local codes, as well as accepted industry practices, and are trained on equipment, procedures, and applications involved. Drawings are not to scale.
Refer to the boiler, control and module installer manuals for additional detailed information!
Data subject to change
BOSC BOILER (2) = YES
BOSC MODL (2) = "SB-Series"
ENABLE (3) = OFF
ENABLE (4) = OFF
IDHW LOCATION = PRIM
IDHW SENSOR = ON
IDHW PRIM PUMP = OFF
S5 =
Boiler Inlet Sensor
S6, S7 = Boiler Outlet Sensors
S8 =
Vent Sensor
P1 =
Primary Pump
S8
S7
SB Series
S5
Features:
The boiler plant is sequenced to obtain
maximum efficiency based on the boiler
types & target temperatures. For detailed
information about sequencing, rotation &
staging, refer to the Installation & Operation
Manual.
Outdoor Temperature Reset saves energy
by operating the boiler plant using the
lowest possible temperatures. Lower water
temperatures ensure modulating condensing
boilers operate at maximum efficiency.
Optional indirect DHW (IDHW) priority.
Boiler ∆T monitoring is available when using
optional boiler outlet sensors (S6 & S7) and
boiler inlet sensor (S5).
The Common Flue Sensor (S8) is optional.
P4 =
IDHW Pump
S4
P4
S2
P1
S3
Applications Manual
DIP Settings:
External Flow Proof
/ Off
External C.A. Proof
/ Off
S1