Connecting EC transmitter to NMC-64 controller

Connect EC transmitter to NMC-64 analog input card as follows:
• EC transmitter's connector 1 to analog card's connector Red.
• EC transmitter's connector 2 to analog card's connector T5.
• Check that analog card's jumper 1 (from left) is set to 4-20mA.
T5
Red
12VDC
Input
(example – using Milwaukee 1413 µS/cm solution transmitter
1
2
94