If you delete a row (by zeroing the Mist .No.) it will be pushed to the end of the table
and the rest of the rows will jump one step up. Pressing the menu key does this
sorting.
When misting is on, the misting, the main valve and pump operate.
When misting is off, only the pump continues to operate.

1.10 WATER HEATING

WATER HEATING
From Time
To Time
Water Temperature
Difference
Temp. Sensor #1
Temp. Sensor #2
The Water Heating operates according to temperature only within a set time frame
and can be used to increase irrigation water temperature or prevent frost.
• From Time (hh:mm) – Set the start time of the water heating program.
• To Time (hh:mm) – Set the end time of the water heating program.
The water-heating program will only be operative in the defined window of
opportunity (between start "From Time" to end "To Time").
• Water Temperature - Water heating will be activated when the temperature drops
below this value.
• Difference – dead-band for stopping water heating. When the water temperature
reaches the set Water Temperature + Difference water heating will be stopped.
For Example: Water temperature is 25ºC and the difference is 2ºC.
Water heating will start at 25ºc and will stop at 27
Minimum difference is 0.3ºC and the default is 0.5ºC.
• Temp. Sensor 1/2 – assign up to 2 temperature sensors. If you assign 2 sensors,
the NMC-64 will operate according to their average.
00:00
06:00
25.0
2.0
1
3
33
o
.
Software