Wiring - Panasonic FP0-A21 Technical Manual

Programmable controller fp0 a/d converter unit
Hide thumbs Also See for FP0-A21:
Table of Contents

Advertisement

FP0 A/D Converter Unit
2.1

Wiring

Voltage input
V0
I 0
V1
I 1
COM
V2
I 2
V3
I 3
V4
I 4
V5
I 5
COM
V6
I 6
V7
I 7
Connect input instrument between V terminal and COM
terminal.
Notes
Tie the COM connectors for two channels together as indicated by the
black circles (" ") in the diagram above so that no more than two
wires go to each COM terminal.
The two COM terminals are connected internally.
We recommend that you use dual−core twisted pair shielded wiring
for the analog input wiring, and that you connect the shield to earth.
V
COM
Input instrument
(ch0)
Input instrument
(ch1)
Input instrument
(ch2)
Input instrument
(ch3)
Input instrument
(ch4)
Input instrument
(ch5)
Input instrument
(ch6)
Input instrument
(ch7)
Input instrument
Connection to Input Devices
Current input
V0
I 0
V1
I 1
COM
V2
I 2
V3
I 3
V4
I 4
V5
I 5
COM
V6
I 6
V7
I 7
First, connect both V terminal and I terminal. And then
connect input instrument between it and COM terminal.
2.1
Wiring
Input instrument
(ch0)
Input instrument
(ch1)
Input instrument
(ch2)
Input instrument
(ch3)
Input instrument
(ch4)
Input instrument
(ch5)
Input instrument
(ch6)
Input instrument
(ch7)
2 − 3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fp0-a80

Table of Contents