Displaying C-NET devices

7.3 Displaying C-NET devices
52 | 62
Building Technologies
Fire Safety
After auto-configuration, the individual C-NET detector lines and the associated C-
NET devices of each line can be displayed and configured.
Depending on the control panel type (2 or 4 loops) and the control panel design,
the depiction may vary and several lines may be displayed.
You can display the lines and devices as follows. The displays are depicted in the
same way as those in the 'Auto-configuring a line' chapter with the exception of the
'Show details' command.
ϖ At least one line is configured.
1. In the main menu, select the 'Topology' menu item.
 The 'Topology' window is open.
2. Select 'Hardware tree'.
 The 'Element' window is open.
3. Select 'Station' and press the 'Lower level' <softkey>.
 The elements of 'Station' are displayed.
4. Select the corresponding 'C-NET line card (onboard/FCL2001)' Module and
press the 'Lower level' <softkey>.
 All lines of 'C-NET line card (onboard/FCL2001)' are indicated.
5. Select a line and press 'More Options'' <softkey>.
 The 'Select option' window is open.
6. Select 'Execute commands' and confirm with <ok>.
 The window including the possible commands is displayed.
7. Select the 'Show details' command and confirm with <ok>.
 The details are displayed.
A6V10211094_f_en_--
2015-12-15