Download  Print this page

Siemens FC72x Quick Reference Manual Page 35

Fire control panel, fire terminal.
Hide thumbs

Advertisement

Device type
Type
FDOOT271
Neural radio fire
detector (SWING)
Radio manual call
FDM273
point (SWING)
FDM275
Aspirating smoke
VLF
detector
Building Technologies
Fire Safety
Description
Optical-thermal fire detector with radio
transmission to the radio gateway
FDCW241
1
Indirect activation via radio gateway
FDCW241
SWING manual call point, activation via
radio gateway FDCW241
VESDA LaserFocus (laser monitoring)
Table 1: Devices which can be connected to the C-NET detector line
X
Possible / available
Not possible / not available
Availability is communicated with the delivery release
1
Check with your country representative that this detector is approved for
2
C-NET in your country.
Most devices are supplied via the detector line.
The input/output module FDCIO223 must have an external power supply.
All ↑ C-NET devices have an integrated line separator.
NOTICE
Influencing the earth fault monitoring
Faults
For devices on the C-NET with a separate supply, the supply must be
electrically isolated. FDCIO223 is an exception to this rule.
The number of connectable devices depends on the specific AK, RK, MK
connection factor of the type and is calculated using the 'Quantities Tool' software.
Note the specifications of the individual C-NET devices in the 'List of Compatibility'
document, see 'Applicable documents' chapter.
See also
1 C-NET detector line [➙ 31]
Installation
Connectable C-NET devices
↑ AI
Ext. AI
X
X
X
X
A6V10211094_f_en_--
5
DBS 720
35 | 62