Installation; Service Space: Heat Reclaim Ventilation Unit; Unit Orientation - Daikin VAM350J7VEB Installer And User Reference Manual

Heat reclaim ventilation unit
Hide thumbs Also See for VAM350J7VEB:
Table of Contents

Advertisement

6

Installation

6.1
Service space: Heat reclaim
ventilation unit
>1000
a
>600
>50
a
Service space
6.2

Unit orientation

The following illustration helps you to install the heat reclaim
ventilation unit in the correct position:
VAM350~2000J7VEB
Heat reclaim ventilation unit
4P487293-1A – 2018.05
150-250
(mm)
INFORMATION
When the unit is installed vertically, the installer must
provide a support under the unit to distribute the weight of
the unit between the support and the installation bolts in
the wall.
NOTICE
When the heat reclaim ventilation unit is installed vertically
in low outdoor temperature conditions, dewing or freezing
may occur. If such operating conditions are to be expected,
take the appropriate precautions, e.g. install an electrical
heater.
Installation tips:
▪ Installing the unit upside down allows for common use of the
inspection hole, thus reducing the required maintenance space.
For example, if 2 units are installed closely together, only 1
inspection hole is required for maintaining or replacing filters, heat
exchange elements,...
a
c
b
a
Control box
6 Installation
Installer and user reference guide
15