ABB REM615 ANSI 5.0 FP1 Product Manual page 35

Motor protection and control
Table of Contents

Advertisement

Table 48. Motor load jam protection (JAMPTOC)
Characteristc
Operation accuracy
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Table 49. Motor load jam protection (JAMPTOC) main settings
Parameter
Operation
Start value
Operate delay time
Table 50. Motor start-up supervision (STTPMSU)
Characteristic
Operation accuracy
Start time
(1), (2)
I
= 1.1 × set Start
Fault
detection A
Operate time accuracy
Reset ratio
1 Current before = 0.0 × I
, f
= 50 Hz, overcurrent in one phase, results based on statistical distribution of 1000 measurements
n
n
2 Includes the delay of the signal output contact
Table 51. Motor start-up supervision (STTPMSU) main settings
Parameter
Motor start-up A
Motor start-up time
Lock rotor time
Operation
Operation mode
Restart inhibit time
Function
JAMPTOC
JAMPTOC
JAMPTOC
Value
Depending on the frequency of the measured current: f
±1.5% of the set value or ±0.002 x I
Minimum
27 ms
±1.0% of the set value or ±20 ms
Typically 0.90
Function
STTPMSU
STTPMSU
STTPMSU
STTPMSU
STTPMSU
STTPMSU
Value
Depending on the frequency of the measured current: f
±1.5% of the set value or ±0.002 × I
Typically 40 ms
Typically 0.96
<35 ms
±1.0% of the set value or ±20 ms
Value (range)
1 = on
5 = off
0.10...10.00 × I
n
100...120000 ms
±2 Hz
n
n
Typical
30 ms
Value (range)
1.0...10.0 × I
n
1...80 s
2...120 s
1 = on
5 = off
1 = IIt
2 = IIt, CB
3 = IIt + stall
4 = IIt + stall, CB
0...250 min
±2 Hz
n
n
Step
0.01
10
Maximum
34 ms
Step
0.1
1
1
1
35