28
R E M 6 1 5 A N S I 5 . 0 F P 1 M OTO R P R OT E C T I O N A N D C O N T R O L
—
Table 24. Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance measurements
Protective bonding resistance
—
Table 25. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Seismic test
—
Table 26. Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
Storage test
1 For relays with an LC communication interface the maximum operating temperature is +70°C
—
Table 27. Product safety
Description
LV directive
Standard
—
Table 28. EMC compliance
Description
EMC directive
Standard
—
Table 29. RoHS compliance
Description
Complies with RoHS directive 2002/95/EC
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
<0.1 Ω, 4 A, 60 s
Type test value
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
IEC 60255-21-3
Type test value
• 96 h at +55ºC
• 16 h at +85ºC
(1)
• 96 h at -25ºC
• 16 h at -40ºC
• 6 cycles (12 h + 12 h) at +25°C...+55°C,
humidity >93%
• 5 cycles (3 h + 3 h)
at -25°C...+55°C
• 96 h at -40ºC
• 96 h at +85ºC
Value
2006/95/EC
EN 60255-27 (2013)
EN 60255-1 (2009)
Value
2004/108/EC
EN 60255-26 (2013)
Value
Reference
IEC 60255-27
IEEE C37.90-2005
IEC 60255-27
IEEE C37.90-2005
IEC 60255-27
IEC 60255-27
Reference
Class 2
Class 2
Class 2
Reference
IEEE C37.90-2005
IEC 60068-2-2
IEEE C37.90-2005
IEC 60068-2-1
IEEE C37.90-2005
IEC 60068-2-30
IEEE C37.90-2005
IEC60068-2-14
IEEE C37.90-2005
IEC 60068-2-1
IEC 60068-2-2