ABB REM615 ANSI 5.0 FP1 Product Manual page 27

Motor protection and control
Table of Contents

Advertisement

Description
Radio frequency interference test
Fast transient disturbance test
• All ports
Surge immunity test
• Communication
• Other ports
Power frequency (50 Hz) magnetic field
immunity test
• Continuous
• 1...3 s
Pulse magnetic field immunity test
Damped oscillatory magnetic field immunity test
• 2 s
• 1 MHz
Voltage dips and short interruptions
Power frequency immunity test
• Common mode
• Differential mode
Conducted common mode disturbances
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Type test value
10 V (rms)
f = 150 kHz...80 MHz
10 V/m (rms)
f = 80...2700 MHz
10 V/m
f = 900 MHz
20 V/m (rms)
f = 80...1000 MHz
4 kV
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
300 A/m
300 A/m
1000 A/m
6.4/16 μs
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Binary inputs only
300 V rms
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
<79 dB (μV) quasi peak
<66 dB (μV) average
<73 dB (μV) quasi peak
<60 dB (μV) average
<40 dB (μV/m) quasi peak, measured at 10 m
distance
<47 dB (μV/m) quasi peak, measured at 10 m
distance
<76 dB (μV/m) peak
<56 dB (μV/m) average, measured at 3 m
distance
<80 dB (μV/m) peak
<60 dB (μV/m) average, measured at 3 m
distance
Reference
IEC 61000-4-6
IEC 60255-26, class III
IEC 61000-4-3
IEC 60255-26, class III
ENV 50204
IEC 60255-26, class III
IEEE C37.90.2-2004
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
IEC 61000-4-5
IEC 60255-26
IEC 61000-4-8
IEC 61000-4-9
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-26, class A
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
27