Dry Operation - Mitsubishi Electric PKH-2GKLA Technical & Service Manual

Series pkh wall mounted
Hide thumbs Also See for PKH-2GKLA:
Table of Contents

Advertisement

DRY OPERATION

Vane
setting notch
*8—9 Refer to page 28~29.
*12
When room temperature is 18°C or below, the compressor cannot operate.
When room temperature rises over 18°C, the compressor starts after a 3-minute time delay.
*13
Compressor ON time is decided by room temperature. Refer to page 28~29.
*14
In dry operation, compressor ON makes the fan speed LOW. Also, when the compressor OFF and the pipe tempera-
ture is 26°C or less, the fan stops, or when the compressor OFF and the pipe temperature is below 6°C, the fan speed
changes to LOW mode.
It is not possible to set the fan speed with the remote controller.
OC231A
DRY
operation
Four-way valve / OFF
NO
Initial dry
operation
YES
Vane initial setting
YES
Room temperature is
18°C or lower
NO
During
compressor ON
YES
3-minute
compressor
operation
YES
NO
Compressor &
thermostat ON
YES
Compressor ON
time completes
YES
10-minute compressor
OFF timer start
Compressor OFF
Fan STOP
1
*8
*12
NO
NO
*9
YES
NO
*14
22
YES
3-minute
time delay
NO
*9
Compressor &
thermostat
ON
NO
10-minute
NO
compressor
OFF
YES
*13
Compressor ON
time set
Compressor ON
*14
Fan speed LOW