Trane UniTrane Installation, Operation And Maintenance Manual page 78

200-1200 cfm fan coil, cabinet heater, low vertical models
Table of Contents

Advertisement

ECM Overview and Setup
Table 38. Configuration settings of the motor control board (for reference only) (continued)
User
Description on
Interface
Unit Label
Name
AiSc
AI Boost Amp
vFlr
AI Floor
Fdbk
PulsePerRev
pvl1
P Value Mtr 1
Ivl1
I Value Mtr 1
pvl2
P Value Mtr 2
Ivl2
I Value Mtr 2
Ai2m
Ht Sens Mk Val F
Ai2b
Ht Sens Bk Val F
AiPu
Ht Sens Resistor
M1rp
Mt 1 Ramp %/sec
m2rp
Mt 2 Ramp %/sec
Ehrp
EH Ramp Accel
Mhrp
Ramp MAX Time
EHdl
EH Fan off delay
Lrpt
Lck Rtr Protect
Ehpt
Protect Funct
rpdf
Rmp dft (auto rst)
soft
Soft Rev
78
Typical User
Interface
Value
Boosts or attenuates the analog input signal to
1
compensate for long wire runs.
Rejects noise on the analog input lines and sets
up the motor control board to turn on if the
.
0
5
thermostat or controller is commanding its
analog outputs on.
Sets up the tachometer function to be
18
compatible with the on-board motor and for
correct speed calculation and calibration.
Sets up the on board closed loop control to
.
0
03
control Motor 1 with proper stability.
Sets up the on board closed loop control to
.
0
03
control Motor 1 with proper stability.
Sets up the on board closed loop control to
.
0
03
control Motor 2 with proper stability.
Sets up the on board closed loop control to
.
0
03
control Motor 2 with proper stability.
Sets the make value for the motor control board
85
triac output based on the thermistor input.
Sets the break value for the motor control board
90
triac output based on the thermistor input.
Sets the input impedance of the thermistor
out
input.
3
Sets the ramp rate for Motor 1, in % per second.
3
Sets the ramp rate for Motor 2, in % per second
Sets the acceleration factor for the electric heat
2
inputs.
Sets the maximum ramp time for both Motor 1
15
and Motor 2 (in seconds).
Selects how long the fan needs to stay on after
15
an electric heat request has been turned off.
Selects whether to use the on-board locked
on
rotor protection function.
This function protects settings on the board that
on
affect the safety of the electric heat system.
This function shortens the ramps for faster unit
commissioning and auto-resets to off after
off
approximately 15 minutes of power-on
operation.
vx.xx
Displays the software version.
Description
1
A value of
should be used if no voltage level
compensation is needed (i.e., voltage peak is at
10 VDC).
Do not change this setting as this is critical to
proper unit operation.
Do not change this setting.
Do not change this setting.
Do not change this setting.
Do not change this setting.
Fprv
Operation also depends on
Aipu
settings.
Fprv
Operation also depends on
Aipu
settings.
Should be pre-set to "OUT" for Tracer® ZN
controllers.
Is used to force faster ramps when electric heat
is requested.
M1rp
Overrides the ramp rates
the
calculated ramp time exceeds
Not used on fan-coil unit.
This will shut down the affected motor, if
rotational response is not detected.
Do NOT change this setting. This setting locks out
the following parameters from being changed, for
safe operation of the unit.
AiPU
FPrv
AiMK
AiBK
E1M1
E1M2
E2M1
E2M2
Sig
Mod1
Mod2
M1Hi
M1Lo
To aid in commissioning of the unit, for
approximately 10–15 minutes, the ramps will be
shortened to quickly observe proper unit
behavior and response to speeds.
Module should be received with most recent
version.
Ai2B
,
, and
Ai2m
,
, and
M2rp
and
if
Mhrp
.
UNT-SVX07J-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Force-floFcFfFckbFclb

Table of Contents