Trane UniTrane Installation, Operation And Maintenance Manual page 105

200-1200 cfm fan coil, cabinet heater, low vertical models
Table of Contents

Advertisement

Binary Inputs
BIP1: Low Temperature Detection Option
The factory hard wires the low temperature detection
sensor to binary input #1 (BIP1). The sensor defaults
normally closed (N.C.), and will trip off the unit on a low
temperature diagnostic when detecting low temperature.
In addition, the controller controls the unit devices below:
Fan: Off
Valves: Open
Electric heat: Off
Damper: Closed
BIP2: Condensate Overflow Detection Option
The factory hard wires the condensate overflow sensor to
binary input #2 (BIP2). The sensor defaults normally
closed (N.C.), and will trip off the unit on a condensate
overflow diagnostic if condensate reaches the trip point. In
addition, the controller controls the unit devices below:
Fan: Off
Valves: Closed
Electric heat: Off
BIP3: Occupancy Sensor
Binary input #3 (BIP3) is available for field-wiring an
occupancy sensor, such as a binary switch or a timeclock,
to detect occupancy. The sensor can be either normally
open (N.O.) or normally closed (N.C.). Refer to
Table 44. Occupancy sensor state table
Sensor Type
Sensor Position
Normally open
Open
Normally open
Closed
Normally closed
Open
Normally closed
Closed
Binary Outputs
Table below shows the six binary outputs.
Table 45. Binary outputs
Binary output
Description
BOP1
Fan high speed
BOP2
Fan medium speed
BOP3
Fan low speed
1
BOP4
Main valve
1
BOP5
Auxiliary valve/electric heat
2
BOP6
2-position fresh air damper
1
In a four-pipe application, BOP4 is used for cooling and BOP5 is used
Note:
for heating. If no valves are ordered with the unit, the factory defaults
are:
- BOP4 configured as normally closed (N.C.)
- BOP5 configured as normally open (N.O.)
2
If the fresh air damper option is not ordered on the unit, BOP6 will
Note:
be configured as none.
®
Both Tracer
ZN010 and ZN510 accept a maximum of five
analog inputs. See the table below.
UNT-SVX07J-EN
Table
44.
Unit Occupancy Mode
Occupied
Unoccupied
Unoccupied
Occupied
Pin
J1-1
J1-2
J1-4
J1-5
J1-6
J1-7
Table 46. Analog inputs
Analog
Input
Description
Space
Zone
temperature
Set
Local setpoint
Fan
Fan mode input
Analog input 1
Entering water
(AI1)
temperature
Analog input 2
Discharge air
(AI2)
temperature
Notes: - Wall-mounted sensors include a thermistor soldered to the
sensor's circuit board
- Unit mounted sensors include a return air sensor in the unit's
return air stream.
Changeover units include an entering water temperature sensor.
The zone sensor, entering water temperature sensor, and
the discharge air temperature sensor are 10 KΩ
thermistors. See the figure below for the resistance-
temperature curve for these thermistors.
Figure 97.
Resistance temperature curve for the zone
sensor, entering water temperature sensor,
and discharge air sensor
Zone Sensors
The available zone sensors (see
p.
91) provide up to three different inputs:
Space temperature measurement (10 KΩ thermistor)
Local setpoint
Fan mode switch
Wall-mounted zone sensors include a thermistor as a
component of the internal printed circuit board. Unit
mounted zone sensors use a sensor placed in the unit's
return air stream.
Each zone sensor is equipped with a thumb wheel for
setpoint adjustment.
Fan Mode Switch
The zone sensor may be equipped with a fan mode switch.
The fan mode switch offers selections of off, low, medium,
high, or auto.
Supply Fan Operation
Refer to
Table 47
for fan mode operation. The controller
will operate in either continuous fan or fan cycling mode.
The fan cycles when the fan mode switch is placed in auto.
Startup
Application
Space temperature detection /
timed override detection
Thumbwheel setpoint
Zone sensor fan switch
Entering water temperature
detection
Discharge air temperature
detection
"Zone Sensor Options, "
105

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Force-floFcFfFckbFclb

Table of Contents