Trane UniTrane Installation, Operation And Maintenance Manual page 62

200-1200 cfm fan coil, cabinet heater, low vertical models
Table of Contents

Advertisement

Installation - Electrical
MCA = 1.25 x (heater amps + all motor FLAs)
MOP = (2.25 x largest motor FLA) + second motor FLA +
heater amps (if applicable)
Select a standard fuse equal to or less than the MOP . The
selected fuse must be larger than the MCA.
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60
amps
Fan-coil electric heat MBh = (heater kW) (3.413)
Table 33. Force-Flo single-stage, max kW electric heat
Unit
Voltage
# Wires
Size
208/60/1
240/60/1
277/60/1
208/60/3
02
240/60/3
480/60/3
220-240/50/1
220-240/50/3
380-415/50/3
208/60/1
240/60/1
277/60/1
208/60/3
03
240/60/3
480/60/3
220-240/50/1
220-240/50/3
380-415/50/3
208/60/1
240/60/1
277/60/1
208/60/3
04
240/60/3
480/60/3
220-240/50/1
220-240/50/3
380-415/50/3
62
Heater amps/
Heater kW
ph
2
2.25
10.90
2
3.00
12.50
2
3.00
10.90
3
2.25
6.30
3
3.00
7.30
4
3.00
3.70
2
3.00
12.50
3
3.00
7.30
4
3.00
4.20
2
4.50
21.70
2
6.00
25.00
2
6.00
21.70
3
4.50
12.60
3
6.00
14.50
4
6.00
7.30
2
6.00
25.00
3
6.00
14.50
4
6.00
8.40
2
5.70
27.50
2
7.50
31.30
2
7.50
27.10
3
5.70
15.90
3
7.50
18.10
4
7.50
9.10
2
7.50
31.30
3
7.50
18.10
4
7.50
10.50
Table 33. Force-Flo single-stage, max kW electric heat
208/60/1
240/60/1
277/60/1
208/60/3
06
240/60/3
480/60/3
220-240/50/1
220-240/50/3
380-415/50/3
2
7.90
38.00
2
10.50
43.80
2
10.50
38.00
3
7.90
21.90
3
10.50
25.30
4
10.50
12.70
2
10.50
43.80
3
10.50
25.30
4
10.50
14.70
UNT-SVX07J-EN