Trane UniTrane Installation, Operation And Maintenance Manual page 113

200-1200 cfm fan coil, cabinet heater, low vertical models
Table of Contents

Advertisement

Table 57.
Zone Sensor Thermistor Curve (Resistance in Ohms)
°C
°F
R
0
32
32885
1
33.8
31238
2
35.6
29684
3
37.4
28216
4
39.2
26830
5
41
25520
6
42.8
24282
7
44.6
23112
8
46.4
22005
9
48.2
20957
10
50
19966
11
51.8
19028
12
53.6
18139
13
55.4
17297
14
57.2
16499
15
59
15743
16
60.8
15025
17
62.6
14345
18
64.4
13700
19
66.2
13087
20
68
12505
21
69.8
11953
22
71.6
11428
23
73.4
10929
24
75.2
10455
Zone Sensor
The controller accepts the following zone sensor module
inputs:
Space temperature measurement (10kΩ thermistor)
Local setpoint (either internal or external on the zone
sensor module)
Fan switch
Timed override (On) and Cancel timed override
Communication jack
Space Temperature Measurement
Trane zone sensors use a 10kΩ thermistor to measure the
space temperature. Typically, zone sensors are wall-
mounted in the room and include a space temperature
thermistor. As an option, the zone sensor can be unit-
mounted with a separate space temperature thermistor
located in the unit's return air stream. If both a hard-wired
and communicated space temperature value exist, the
UNT-SVX07J-EN
°C
°F
R
25
77
10004
26
78.8
9557
27
80.6
9135
28
82.4
8737
29
84.2
8362
30
86
8007
31
87.8
7672
32
89.6
7355
33
91.4
7056
34
93.2
6772
35
95
6503
36
96.8
6248
37
98.6
6006
38
100.4
5777
39
102.2
5559
40
104
5352
41
105.8
5156
42
107.6
4969
43
109.4
4791
44
111.2
4621
45
113
4460
46
114.8
4306
47
116.6
4160
48
118.4
4020
49
120.2
3886
°C
°F
R
50
122
3759
1
123.8
3597
52
125.6
3445
53
127.4
3301
54
129.2
3165
55
131
3037
56
132.8
2915
57
134.6
2800
58
136.4
2691
59
138.2
2588
60
140
2490
61
141.8
2397
62
143.6
2309
63
145.4
2225
64
147.2
2145
65
149
2070
66
150.8
1998
67
152.6
1929
68
154.4
1864
69
156.2
1802
70
158
1742
71
159.8
1686
72
161.6
1632
73
163.4
1580
74
165.2
1531
controller ignores the hard-wired space temperature input
and uses the communicated value.
External Setpoint Adjustment
Zone sensors with an external setpoint adjustment (1kΩ)
provide the controller with a local setpoint (50°F to 85°F or
10°C to 29.4°C). The external setpoint is exposed on the
zone sensor's front cover.
When the hard-wired setpoint adjustment is used to
determine the setpoints, all unit setpoints are calculated
based on the hard-wired setpoint value, the configured
setpoints, and the active mode of the controller. The hard-
wired setpoint is used with the controller's occupancy
mode (occupied, occupied standby, or unoccupied), the
heating or cooling mode, the temperature deadband
values, and the heating and cooling setpoints (high and
low limits) to determine the controller's active setpoint.
When a building automation system or other controller
communicates a setpoint to the controller, the controller
ignores the hard-wired setpoint input and uses the
communicated value. The exception is the unoccupied
Startup
°C
°F
R
75
167
1484
76
168.8
1436
77
170.6
1389
78
172.4
1345
79
174.2
1302
80
176
1260
81
177.8
1220
82
179.6
1182
83
181.4
1145
84
183.2
1109
85
185
1074
86
186.8
1041
87
188.6
1009
88
190.4
978
89
192.2
948
90
194
920
91
195.8
892
92
197.6
865
93
199.4
839
94
201.2
814
95
203
790
96
204.8
767
97
206.6
744
98
208.4
722
99
210.2
701
113