en | Exchanging and Adding Radio Components
8

Exchanging and Adding Radio Components

Notice!
As soon as one or more RF detectors are removed, the complete RF fire detection system
must be set up again, as described in chapter Commissioning a RF Fire Detection System, page
20.
8.1
Exchanging the FK 100 LSN RF Interface Module and DOW
1171 and SMF121 RF Detectors
Notice!
You can only exchange a RF interface module or RF detector using WinPara or FSP‑5000‑RPS.
Exchanging the FK 100 LSN RF Interface Module
1.
2.
Exchanging DOW 1171 and SMF121 RF Detectors
1.
2.
3.
4.
5.
8.2
Adding DOW 1171 and SMF121 RF Detectors using WinPara /
FSP‑5000‑RPS
1.
2.
3.
4.
5.
8.3

Manually Adding DOW 1171 and SMF121 RF Detectors

1.
2016.04 | 6.0 | 4.998.120.885
After exchanging the RF interface module, load the current WinPara / FSP-5000-RPS in
the fire panel. The new RF interface module thus recognizes the number of RF detectors.
Then set up the complete RF fire detection system again, as described in chapter
Commissioning a RF Fire Detection System, page 20.
Highlight the RF detector to be exchanged in WinPara / FSP-5000-RPS.
In WinPara / FSP-5000-RPS, activate menu item Exchange detector DOW 1171 / SMF or
Exchange DOW 1171 / SMF.
Wait until the red LED on the DOW 1171 RF Smoke Detector or the green LED on the PC
board in the SMF6120 Detector Base as well as the green LED on the FK 100 LSN RF
Interface Module are flashing rapidly.
Now take the DOW 1171 RF Smoke Detector out of the base or disconnect the SMF121
Manual Call Point including the SMF6120 Detector Base.
To log in the new RF detectors, follow the instructions in chapter Logging in DOW 1171 RF
Smoke Detectors to the RF Interface Module, page 21 or chapter Logging in the SMF121 RF
Manual Call Points to the RF Interface Module, page 22.
In WinPara / FSP-5000-RPS under FK 100 -> LSN, call up menu item Add under or Add
DOW 1171 / SMF.
Enter the number of new RF detectors.
Save the configuration and load it into the fire panel.
In WinPara / FSP-5000-RPS under FK 100, activate menu item DOW 1171 / SMF121 to be
added or Send add for DOW 1171 / SMF121. Confirm in WinPara with Yes.
The green LED on the RF interface module flashes rapidly and shows that the RF
detectors can now be added.
To log in the RF detectors, follow the instructions in chapter Logging in DOW 1171 RF
Smoke Detectors to the RF Interface Module, page 21 or chapter Logging in the SMF121 RF
Manual Call Points to the RF Interface Module, page 22.
Make sure that the power supply to the RF interface module has been disconnected. If
required, pull out the terminal block for the power supply.