Commissioning The Fk 100 Lsn Rf Interface Module Via Winpara / Fsp-5000-Rps; Commissioning Dow 1171 And Smf121 Rf Detectors; Logging In Dow 1171 Rf Smoke Detectors To The Rf Interface Module - Bosch DOW 1171 Operation Manual

Radio frequency fire detection system
Table of Contents

Advertisement

Radio Frequency Fire Detection System
In the input field in the Read out dynamic data menu, under item Periphery control, enter "Type
10" as text. You will see the base channel in the display under Data. FSP-5000-RPS does not
support this function.
However, you can also read off the B-channel direct from the FPA-5000 Fire Panel. Go to
Diagnostics -> Element Details, and select the appropriate LSN module to display the relevant
RF interface module using All info for one element -> by description or -> by number. The HF
channel describes the number of the B-channel.
7.1
Commissioning the FK 100 LSN RF Interface Module via
WinPara / FSP-5000-RPS
1.
2.
3.
7.2

Commissioning DOW 1171 and SMF121 RF Detectors

Notice!
It must be possible to clearly locate triggered detectors. For this reason, log in all the RF
detectors one after the other and in the sequence in which they are entered in WinPara /
FSP-5000-RPS.
Ensure that all the DOW 1171 and SMF121 RF Detectors are installed in the appropriate base
and at the actual installation location when logging in to the RF interface module.
7.2.1

Logging in DOW 1171 RF Smoke Detectors to the RF Interface Module

1.
2.
3.
Once the detector has been logged into the RF interface module, the red LED on the detector
goes out and then starts to flash again for approx. 2 minutes. The flash rate shows the field
strength (quality of the radio connection).
Bosch Sicherheitssysteme GmbH
Insert the wired terminal blocks for LSN and power supply in the RF interface module
(wiring see chapter Connection of FK 100 LSN RF Interface Module to the Fire Panel, page
18).
The red LED on the RF interface module lights up for approx. 10 seconds. Then the yellow
LED flashes slowly.
If this is not the case, the RF interface module must be manually reset to the delivery
state (see chapter Resetting the RF Interface Module to the Delivery State, page 26).
Configure all the RF interface modules and planned RF detectors in WinPara / FSP-5000-
RPS and load the configuration into the fire panel using PC/laptop.
In WinPara / FSP-5000-RPS, activate menu item Reset FK 100 or Initialize FK 100.
The red LED on the RF interface module lights up for approx. 10 seconds. As soon as it
goes out, the green and yellow LEDs start to flash rapidly and the automatic search for a
base channel (frequency) starts. After a successful search (approx. 1 to 5 minutes), the
yellow LED goes out and the green LED flashes until all the RF detectors configured in
WinPara / FSP-5000-RPS are logged in.
Connect the batteries in the detector base.
The red LED on the detector starts to flash slowly.
If the red LED flashes rapidly after inserting the batteries, the detector must be reset to
the delivery state. To do this, press the new button in the detector base for at least 3
seconds.
Insert the detector into the base within 10 minutes. As soon as the detector has been
inserted, it starts logging in.
Now log in all the detectors one after the other. In so doing, take note of the sequence
entered in the WinPara- / FSP-5000-RPS configuration.
Commissioning a RF Fire Detection System | en
Operation Guide
21
2016.04 | 6.0 | 4.998.120.885