8 | Information for heating contractor
Systems with several heating circuits (zone controller/remote control)
▶ A.1 = Set and confirm SC (zone controller).
-or-
▶ A.1 = Set and confirm Fb (remote control)
▶ Select and confirm heating circuit (HC = 1...8).
4.5

Settings in the service menu

Setting
Adjustment range
A.1
CO | Fb | SC
HC
HC1 | HC2 | ... | HC7 |
HC8
d.1
2 | 3 | 4
E.1
– 3.0 ... 0.0 ... 3.0
P.1
4 | 5
L 1
1 | 0
C.1
C | F
CR 10
1)
Description
Controller (CO), remote control (Fb), zone
controller (SC)
Heating circuit/heating zone 1 to 8
Control characteristics (reaction speed)
2: 2K P range = Quick reaction
3: 3K P range = Medium reaction
4: 4K P range = Slow reaction
Correction value for the room temperature
displayed
Flow temperature control (4) or output
control (5)
Optimised running of the pump: in the case
of flow temperature control, the heating
pump runs as briefly as possible.
Switching-off if there is a buffer cylinder in
the system.
Unit of displayed temperatures °C (C) or °F
(F)
°C
°F
2)
6720830560 (2015/06)
°C
°F
°C
°F
°C
°F