Using the RE5000AD with a
RE5000 System
Installation and Operating
Introduction
When connected to the RE5000
RE5000AD may be used to communicate up to three
separate message phrases (usually relating to Intruder,
Fire and Medical Alert conditions). The Dialler Tamper
Switch may be connected to Zone 6 on the RE5000CU
if tamper protection is required.
The Communicator Interface Cable connection supplied
with the RE5000 Control Unit allows simple connection
between the Control Unit and Dialler.
THE FOLLOWING MUST BE READ IN CONJUNCTION
WITH THE RE5000AD (TSD1+) INSTALLATION AND
OPERATING INSTRUCTIONS SUPPLIED AND THE
RE5000 INSTALLATION AND OPERATING MANUAL.
Note:
If your RE5000CU is supplied with an
interface cable, please call our Technical
Helpline for connection advice.
9
Optional Dialler Tamper Connection
CORE
To Zone 6 Hard Wired Zone Input
N.O.
COM
9-Core Interface Cable
N.C.
V+
GRD
Zone 6
Siren
Charge
Tamper

Control Unit

Terminal Block
Communicator
Interface Cable
Connection
Plug-in Connector to Control Unit PCB
Control Unit, the
8-Core
Factory
Restart Pins
on RE5000CU
Red +12V
AC Power
Blue
Failure
Grey
– 0V
Brown
Arm
Orange
Disarm
Yellow
Low Batt
Green
Intruder
Mauve
Fire
Medical Alert/
White
Personal Attack
Control Unit
Instructions
CONNECTING THE RE5000AD TO
THE RE5000 CONTROL UNIT.
1.
Disconnect all power (Mains and Back-up Battery)
from the Control Unit before making any connections.
2. Plug the Interface Cable into the Control Unit plug
and connect the lead to the Dialler as shown.
3. Ensure that all cabling is connected correctly and that
all unused cores of the Interface Cable are cut back or
insulated to prevent accidental short circuits.
4. Connect the Telephone Cable to the Dialler - (see
Dialler Installation Instructions).
5. Reconnect power to the Control Unit and proceed to
programme and test the Dialler in accordance with
the Dialler Operators Manual.
Loudspeaker
Tamper
Switch
TSD1 +
0/P1
0V
+12V
Connections for
Microphone
TRIG INPUT
TAMP ABORT C
B
A
TRIGGER
POLARITY
Set Trig Polarity
negative trigger
to suit RE5000CU
Telephone Line
Connection Terminals
9-Core Interface Cable
Link to '+' for
trigger output

Advertisement

loading

Summary of Contents for Response RE5000AD

  • Page 1: Control Unit

    When connected to the RE5000 Control Unit, the Disconnect all power (Mains and Back-up Battery) RE5000AD may be used to communicate up to three from the Control Unit before making any connections. separate message phrases (usually relating to Intruder, Fire and Medical Alert conditions). The Dialler Tamper 2.
  • Page 2 When connected to the RE3000 Control Unit, the Disconnect all power (Mains and Back-up Battery) RE5000AD may only be used to communicate one from the Control Unit before making any connections. message phrase associated with the Alarm Activation - (usually relating to an Intruder Alarm Condition).

This manual is also suitable for:

Re5000