6. Wiring

6.1 Wiring precautions

To obtain maximum performance from the functions of AJ65SBT-64AD and
improve the system reliability, an external wiring with high durability against noise
is required.
The precautions when performing external wiring are as follows:
(1) Use separate cables for the AC and AJ65SBT-64AD external input signals,
in order not to be affected by the AC side surge or conductivity.
(2) Do not bundle or place with load carrying wires other than the main circuit
line, high voltage line or programmable controller. Noises, surges, or
conductivity may affect the system.
(3) Place a one-point grounding on the programmable controller side for the
shielded line or shielded cable. However, depending on the external noise
conditions, it may be better have a grounding externally.

6.2 Module connection example

For voltage input
Signal source 0 to ±10 V
For current input
Signal source 0 to ±20mA
*1 Use a two-core twisted shield line for the power cable.
*2 Indicates the AJ65SBT-64AD input resistor.
*3 For the current input, be sure to connect the (V+) and (I+) terminals.
*4 When noise or ripple occurs with the external cable, connect a condenser with
about 0.1 to 0.47µF (25V or higher voltage-resistant product) between the
terminal V and COM.
*5 Always perform grounding for FG1. When there is a lot of noise, it may be
better ground AG as well.
If the grounding wiring (grounding yes/no) is changed after the offset and gain
are set, perform the setting of the offset/gain values again.
*4
CH1
COM
SLD
*1 Shield
CH4
*3
COM
SLD
*1 Shield
*5
FG1
8
500k
V+
250
I+
500k
*2
500k
V+
I+
500k
250
AG