e.2.6.3 Setup Engineering Units Display
Press the UP or DN button, to change current engineering units. The following engi-
neering units are supported: %F.S., SLPM, SLPH, SCCM, SCCH, SCFM, SCFH, SCMM,
SCMH, LBPM, LBPH, GRPM, GRPH. If no more settings are required, press the ENTER
button under EXIT on the display, to go back to the Main Display. Press the ENTER but-
ton under NEXT on the display in order to go to the Full Scale Flow Rate screen. The
following Setup Full Scale Flow Rate Display will appear.
e.2.6.4 Setup Full Scale Flow Rate Display
The proper settings of the Full Scale Flow Rate (in liters per minute) are required for any
engineering units except % F.S. If for example a mass flow controller used with
SDPROC is calibrated for 200 SCCM, the value of 0.2 has to be set. Press the ENTER
button under (--->) on the display, to move the flashing cursor to the digit, which has
to be adjusted. Pressing (+) or (-) will increment or decrement the particular digit
respectively. The numbers will change from 0 to 9 and next to decimal point (.).
Pressing (+) button one more time will change highlighted position of the cursor back
to 0. The same is true in backward direction when pressing the (-) button. Only one dec-
imal point is allowed. If changing position of the decimal point is required, change the
decimal point to any desired digit, next move cursor to the required position and adjust
it to decimal point with the (+) or (-) button. When complete with Full Scale Flow Rate
settings, press the ESC button under NEXT on the display, to go to the Relays
Assignment screen. The following Setup Relays Assignment Display will appear.
e.2.6.5 Setup Relays Assignment Display
Two sets of dry contact relay are available for each channel. Each relay individually
can be assigned for:
= NO ACTION
= ALARM LOW
= ALARM HIGH
= TOTALIZER STOP
Press UP or DN button to change relay assignment. When complete with first relay
settings, press the ESC button under NEXT on the display, to go to the second relay.
10