Installation Guide
2.0 Settings
2.1 Optimization, summer cut-out
To enable differentiated cut-out temperature based on the time of
the year two dates can be set with different settings of the cut-out
temperature as well as the filtering defining the accumulated
outdoor temperature.
For applications in which the heat cut-out has to run according
to the outdoor temperature only, the settings are to be set in the
"Summer cut-out" menu under "Optimization" for the heating
circuit in question.
This is valid as long as the dates for "Summer" and "Winter" in the
"Heat cut-out" menu are the same (factory setting).
Summer cut-out (limit for heating cut-out)
Circuit
1*)
*) depending on application
The heating can be switched OFF when the outdoor temperature is
higher than the set value. The valve closes and after the post-run
time, the heating circulation pump stops. 'Temp. min. ' will be
overruled.
The heating system switches ON again when the outdoor
temperature and the accumulated (filtered) outdoor temperature
become lower than the set limit.
4
DEN-SMT/DK
ECL Comfort 210 and 310, extended heat cut-out
11179
Factory setting
Setting range
OFF / 1 ... 50 °C
20 °C
Temp.
Actual outdoor temp.
18 °C
Heating ON
VI.GU.U1.02
Accumulated outdoor temp.
Heating OFF
Heating ON
Danfoss District Energy
Time
Need help?