Figure 1. Burner Nameplate
General Model Information
Serial Number,
Including Date Code
Rating Information
Approval Agency
Primary Group

Pre-installation Checklist

Combustion air supply

Adequate Combustion and
Ventilation Air Supply
Required
Failure to provide adequate air supply could
seriously affect the burner performance and result in
damage to the equipment and emission of poisonous
carbon monoxide gas.
The burner cannot properly burn the fuel if it is not
supplied with a reliable combustion air source.
Follow the guidelines in the latest edition of National
Fuel Gas Code ANSI Z223.1 (NFPA 54) and
CAN1-B149.1 regarding providing adequate air for
combustion and ventilation.
For appliance/burner units in confi ned spaces, the
room must have an air opening near the top of the
room, plus one near the fl oor, each with a free area
at least one square inch per 1000 Btu/hr input for all
fuel-burning equipment in the room.
CG10 Burner Manual
Symbols
and Fuel
Section: Pre-installation Checklist
R.W. Beckett
Construction and Setting Data
R.W. Beckett Specifi cation
Number and Revision
Boiler Manufacturer and Model,
When Applicable
Additional Codes

Indoor Installation

Protect against Dust and
Moisture
Wet or dusty environments could lead to blocked
air passages, corrosion damage to components,
impaired combustion performance and result in
asphyxiation, explosion or fi re.
This burner is designed for clean, dry installations.
Electrical controls are not protected against rain or
sprayed liquids.
Keep the installation clear of dust, dirt, corrosive
vapors, and moisture.
Protective covers and more frequent maintenance
may be required.
If there is risk of the space being under negative
pressure, or of exhaust fans or other devices depleting
available air for combustion and ventilation, the
appliance/burner should be installed in an isolated room
provided with outside combustion air.