172 Actual signals and parameters
Code
Description
1209
TIMED MODE SEL
Defines timer activated, constant speed mode. Timer can be used to change between
external reference and a maximum of three constant speeds, or to change between a
maximum of 4 selectable speeds, in other words, constant speeds 1,2,3 and 4.
1 = EXT/CS1/2/3 – Selects an external speed when no timer is active, selects
Constant speed 1 when Timer 1 is active, selects Constant speed 2 when Timer 2
is active and selects Constant speed 3 when both Timers 1 and 2 are active.
TIMER1
0
1
0
1
2 = CS1/2/3/4 – Selects Constant speed 1 when no timer is active, selects Constant
speed 2 when Timer 1 is active, selects Constant speed 3 when Timer 2 is active,
selects Constant speed 4 when both timers are active.
TIMER1
0
1
0
1
Group 12: Constant speeds
Range
1...2
TIMER2
Function
0
External reference
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
1
Constant speed 3 (1204)
TIMER2
Function
0
Constant speed 1 (1202)
0
Constant speed 2 (1203)
1
Constant speed 3 (1204)
1
Constant speed 4 (1205)
Resolution
Default
1
2
S