E-Clipse

This macro configures an E-Clipse Bypass device which can bypass the drive and
connect the motor direct on-line. When using direct speed reference in AUTO mode
or process PID, see section
Note: This macro is available only for the UK version.
X1A
1
SCR
2
AI1
3
AGND
4
10V
5
AI2
6
AGND
7
AO1
mA
8
AGND
9
24V
10 GND
11 DCOM
12 DI1
13 DI2
14 DI3
15 DI4
16 DI5
X1B
17 RO1C
18 RO1A
19 RO1B
20 RO2C
21 RO2A
22 RO2B
Parameter
9902
APPLIC MACRO
9802
COMM PROTO SEL
1001
EXT1 COMMANDS
1002
EXT2 COMMANDS
1601
RUN ENABLE
For more information see
General considerations
Signal cable shield (screen)
Not configured
Analog input circuit common
Reference voltage 10 VDC
Not configured
Analog input circuit common
Output frequency: 0(4)...20 mA
Analog output circuit common
Auxiliary voltage output +24 VDC
Auxiliary voltage output common
Digital input common for all
Not configured
Not configured
Not configured
Not configured
Not configured
Relay output 1 (P 1401)
Default operation: Fault (-1) =>20 connected to 22
Digital output (P 1805)
Default operation: Running =>22 connected to 24
Parameters changed relative to HVAC default
Value
15 (E-CLIPSE)
1 (STD MODBUS)
10 (COMM)
10 (COMM)
7 (COMM)
Default values with different macros
Application macros 97
on page 80.
Parameter
1608
START ENABLE 1
5303
EFB BAUD RATE
5304
EFB PARITY
5305
EFB CTRL PROFILE
on page 279.
Value
7 (COMM)
76.8 kb/s
2 (8 EVEN 1)
1 (DCU PROFILE)