Installation
(continued)
1397 150HP AC Line Disconnect
7 a Apply the label to the top front of the AC line disconnect
b Connect the incoming AC power lines to the line side of the
AC line disconnect using the built-in box connectors. Torque
the screws to 28.24 N-m (250 lb.-in.) for 250A disconnects,
and 33.89 N-m (300 lb.-in.) for 400A disconnects.
c Flip the line fuse cover up and press it against the hook and
loop fastener to hold it in position over the fuses.
45
a
A1
81
82
83
A1
GRD
b
b
b
ON
OFF
SET AT "2"
47
1397-5.21
7
c
July, 1997