Configuration Parameters – Module (Page 1)
101
Contrast
0 (%)
117
Use Module RPM
102
Fast Loading Enabled
On (1), Off (0)
118
Use Module Charge Alt
103
All Warnings Latched
On (1), Off (0)
119
Disable CAN Speed Control
104
Lamp Test At Startup
On (1), Off (0)
120
CT Position
105
Power Save Mode Enable On (1), Off (0)
121
Generator Voltage Display
106
Deep Sleep Mode Enable
On (1), Off (0)
122
Mains Voltage Display
107
Protected Start Enable
On (1), Off (0)
123
Generator Frequency Display On (1), Off (0)
108
Event Log Display Format On (1), Off (0)
124
Mains Frequency Display
109
Power Up Mode
0 (Power Up Mode)
125
Current Display
110
DTC String Enable
On (1), Off (0)
126
kW Display
111
RESERVED
127
kVAr Display
Pin Protected
112
On (1), Off (0)
128
kVA Display
Maintenance Reset
113
Stop Button Cooldown
On (1), Off (0)
129
pf Display
114
Use Module Oil Pressure
On (1), Off (0)
130
kWh Display
115
Use Module Coolant Temp On (1), Off (0)
131
kVArh Display
116
Use Module Engine Hours On (1), Off (0)
132
kVAh Display
Configuration Parameters – CAN Application (Page 2)
201
CAN Alternative Engine Speed
On (1), Off (0)
203
CAN ECU Data Fail Action
202
CAN ECU Data Fail Enable
On (1), Off (0)
204
CAN ECU Data Fail Delay
Configuration Parameters – Digital Inputs (Page 3)
301
Digital Input A Source
302
Digital Input A Polarity
303
Digital Input A Action (If Source = User Config)
304
Digital Input A Arming (If Source = User Config)
305
Digital Input A Activation Delay (If Source = User Config)
306
Digital Input B Source
307
Digital Input B Polarity
308
Digital Input B Action (If Source = User Config)
309
Digital Input B Arming (If Source = User Config)
310
Digital Input B Activation Delay (If Source = User Config)
311
Digital Input C Source
312
Digital Input C Polarity
313
Digital Input C Action (If Source = User Config)
314
Digital Input C Arming (If Source = User Config)
315
Digital Input C Activation Delay (If Source = User Config)
316
Digital Input D Source
317
Digital Input D Polarity
318
Digital Input D Action (If Source = User Config)
319
Digital Input D Arming (If Source = User Config)
320
Digital Input D Activation Delay (If Source = User Config)
321-330
RESERVED
331
Analogue Input A (Set As Digital) Source
332
Analogue Input A (Set As Digital) Polarity
333
Analogue Input A (Set As Digital) Action (If Source = User Config)
334
Analogue Input A (Set As Digital) Arming (If Source = User Config)
335
Analogue Input A (Set As Digital) Activation Delay (If Source = User Config)
336
Analogue Input B (Set As Digital) Source
337
Analogue Input B (Set As Digital) Polarity
338
Analogue Input B (Set As Digital) Action (If Source = User Config)
339
Analogue Input B (Set As Digital) Arming (If Source = User Config)
340
Analogue Input B (Set As Digital) Activation Delay (If Source = User Config)
341
Analogue Input C (Set As Digital) Source
342
Analogue Input C (Set As Digital) Polarity
343
Analogue Input C (Set As Digital) Action (If Source = User Config)
344
Analogue Input C (Set As Digital) Arming (If Source = User Config)
345
Analogue Input C (Set As Digital) Activation Delay (If Source = User Config)
Configuration Parameters – Outputs (Page 4)
401 Digital Output A Source
0 (Output Source)
407
Digital Output D Source
402 Digital Output A Polarity
0 (Output Polarity)
408
Digital Output D Polarity
403 Digital Output B Source
0 (Output Source)
409
Digital Output E Source
404 Digital Output B Polarity
0 (Output Polarity)
410
Digital Output E Polarity
405 Digital Output C Source
0 (Output Source)
411
Digital Output F Source
406 Digital Output C Polarity
0 (Output Polarity)
412
Digital Output F Polarity
Pressure Sensor List
Temperature Senor List
Index
Type
Index
Type
0
Not used
0
Not Used
1
Dig Closed for Alarm
1
Dig Closed for Alarm
2
Dig Open for Alarm
2
Dig Open for Alarm
3
VDO 5 Bar
3
VDO 120 °C
4
VDO 10 Bar
4
Datcon High
5
Datcon 5 Bar
5
Datcon Low
6
Datcon 10 Bar
6
Murphy
7
Datcon 7 Bar
7
Cummins
8
Murphy 7 Bar
8
PT100
9
CMB812
9
Veglia
10
Veglia
10
Beru
11
User Defined
11
User Defined
Configuration Parameters – Timers (Page 5)
On (1), Off (0)
501
Mains Transient Delay
On (1), Off (0)
502
Start Delay
On (1), Off (0)
503
Preheat Timer
Gen (0), Load(1)
504
Crank Time
On (1), Off (0)
505
Crank Rest Time
On (1), Off (0)
506
Smoke Limiting
507
Smoke Limiting Off
On (1), Off (0)
508
Safety On Delay
On (1), Off (0)
509
Warm Up Time
On (1), Off (0)
Configuration Parameters – Generator (Page 6)
On (1), Off (0)
601
Alternator Fitted
602
Alternator Poles
On (1), Off (0)
603
Under Voltage Shutdown Enable On (1), Off (0)
On (1), Off (0)
604
Under Voltage Trip Shutdown
On (1), Off (0)
605
Under Voltage Warning Enable
On (1), Off (0)
606
Under Voltage Warning Trip
On (1), Off (0)
607
RESERVED
608
Loading Voltage
0 (Action)
609
Over Voltage Warning Enable
0 s
610
Over Voltage Warning Return
611
Over Voltage Warning Trip
0 (Input Source)
612
Over Voltage Shutdown Trip
0 (Polarity)
Under Frequency Shutdown
0 (Action)
613
Enable
0 (Arming)
614
Under Frequency Shutdown Trip 0.0 Hz
0 s
Under Frequency Warning
0 (Input Source)
615
Enable
0 (Polarity)
616
Under Frequency Warning Trip
0 (Action)
617
RESERVED
0 (Arming)
618
Loading Frequency
0 s
619
Nominal Frequency
0 (Input Source)
Configuration Parameters – Mains (Page 7)
0 (Polarity)
701
AC System
0 (Action)
702
Mains Failure Detection
0 (Arming)
703
Immediate Mains Dropout
0 s
704
Under Voltage Enable
0 (Input Source)
705
Under Voltage Level
0 (Polarity)
706
Under Voltage Return
0 (Action)
707
Over Voltage Enable
0 (Arming)
708
Over Voltage Return
0 s
Configuration Parameters – Engine (Page 8)
0 (Input Source)
801
Start Attempts
0 (Polarity)
802
Over Speed Overshoot
0 (Action)
803
Over Speed Delay
0 (Arming)
Gas Choke Timer
804
0 s
(Gas Engine Only)
0 (Input Source)
Gas On Delay
805
0 (Polarity)
(Gas Engine Only)
0 (Action)
Gas Ignition Off Delay
806
(Gas Engine Only)
0 (Arming)
0 s
Crank Disconnect On Oil
807
Pressure Enable
0 (Input Source)
Check Oil Pressure Prior To
0 (Polarity)
808
Starting
0 (Action)
809
Crank Disconnect On Oil
0 (Arming)
810
Crank Disconnect On Frequency 0.0 Hz
0 s
Crank Disconnect On Engine
811
Speed
0 (Output Source)
812
Under Speed Enable
0 (Output Polarity)
813
Under Speed Trip
0 (Output Source)
814
Over Speed Trip
0 (Output Polarity)
815
Low Battery Voltage Enable
0 (Output Source)
816
Low Battery Voltage Trip
0 (Output Polarity)
Sensor Type
Percentage Sensor List
Index
Type
Index
Type
0
Not Used
0
None
1
Dig Closed for Alarm
1
Digital Input
2
Dig Open for Alarm
2
Percentage Sensor
3
VDO Ohm (10-180)
3
Pressure Sensor
4
VDO Tube (90-0)
4
Temperature Sensor
5
US Ohm (240-33)
6
GM Ohm (0-90)
Digital Input Polarity
7
GM Ohm (0-30)
Index
Polarity
8
Ford (73-10)
0
Close to Activate
9
User Defined
1
Open to Activate
510
Return Delay
519
Delayed Load Output 2
511
Cooling Time
520
Delayed Load Output 3
512
ETS Solenoid Hold
521
Delayed Load Output 4
513
Failed To Stop Delay
522
Power Save Mode Delay
514
Generator Transient Delay
523
Deep Sleep Mode Delay
515
Transfer Time
524
Page Timer
516
Breaker Trip Pulse
525
Cooling Time at Idle
517
Breaker Close Pulse
518
Delayed Load Output 1
On (1), Off (0)
620
Over Frequency Warning Enable
On (1), Off (0)
0
621
Over Frequency Warning Return
0.0 Hz
622
Over Frequency Warning Trip
0.0 Hz
0 V
623
Over Frequency Shutdown Enable
On (1), Off (0)
On (1), Off (0)
624
Over Frequency Shutdown Trip
0.0 Hz
0 V
625
AC System
0 (AC System)
626
CT Primary
0 A
0 V
627
Full Load Rating
0 A
On (1), Off (0)
628
Immediate Over Current Enable
On (1), Off (0)
Delayed Over Current Alarm
0 V
629
On (1), Off (0)
Enable
0 V
630
Delayed Over Current Alarm Action 0 (Action)
0 V
631
Over Current Delay Time
0 s
On (1), Off (0)
632
Over Current Trip
0 %
633
kW Rating
0 kW
On (1), Off (0)
634
Over kW Protection Enable
On (1), Off (0)
0.0 Hz
635
Over kW Protection Action
0 (Action)
636
Over kW Protection Trip
0 %
0.0 Hz
637
Over kW Protection Trip Delay
0 s
0.0 Hz
638* Enable CT Support
On (1), Off (0)
0 (AC System)
709
Over Voltage Level Trip
On (1), Off (0)
710
Under Frequency Enable
On (1), Off (0)
711
Under Frequency Trip
On (1), Off (0)
712
Under Frequency Return
0 V
713
Over Frequency Enable
0 V
714
Over Frequency Return
On (1), Off (0)
715
Over Frequency Trip
0 V
0
817
Low Battery Voltage Return
0 %
818
Low Battery Voltage Delay
0 s
819
High Battery Voltage Enable
0 s
820
High Battery Voltage Return
0 s
821
High Battery Voltage Trip
High Battery Voltage Warning
0 s
822
Delay
On (1), Off (0)
823
Charge Alt Shutdown Enable
On (1), Off (0)
824
Charge Alt Shutdown Trip
0.00 Bar
825
Charge Alt Shutdown Delay
826
Charge Alt Warning Enable
0 RPM
827
Charge Alt Warning Trip
On (1), Off (0)
828
Charge Alt Warning Delay
0 RPM
829
Low Battery Start Arming
0 RPM
830
Low Battery Start Threshold
On (1), Off (0)
831
Low Battery Start Delay
0.0 V
832
Low Battery Start Run Time
Digital Input Alarm
AC System
Power Up Mode
Arming
Index
Type
Index
Arming
Index
0
2 Phase 3 Wire (L1-L2)
0
Always
0
1
2 Phase 3 Wire (L1-L3)
1
From Safety On
1
2
3 Phase 3 Wire
2
From Starting
2
3
3 Phase 4 Wire
3
Never
4
3 Phase 4 Wire (Delta)
5
Single Phase 2 Wire
Output Polarity
Alarm Action
Index
Polarity
Index
Action
0
Energise
0
Electrical Trip
1
De-Energise
1
Shutdown
2
Warning
Configuration Parameters – Analogue Inputs (Page 9)
901
Analogue Input A Senor Type
902
Analogue Input A Sensor Selection
903
Low Oil Pressure Enable
904
Low Oil Pressure Trip
905
Oil Pressure Sender Open Circuit
906
Analogue Input B Senor Type
907
Analogue Input B Sensor Selection
908
High Engine Temperature Trip
909
Temperature Sender Open Circuit
910
Analogue Input C Sensor Usage
911
Analogue Input C Senor Type
912
Analogue Input C Sensor Selection
913
Flexible Sensor C Arming
914
Flexible Sensor C Low Alarm Action
915
Flexible Sensor C Low Alarm Trip
916
RESERVED
917
Flexible Sensor C Low Pre-Alarm Enable
918
Flexible Sensor C Low Pre-Alarm Trip
919
Flexible Sensor C Low Pre-Alarm Return
920
RESERVED
921
Flexible Sensor C High Pre-Alarm Enable
922
Flexible Sensor C High Pre-Alarm Return
923
Flexible Sensor C High Pre-Alarm Trip
924-925 RESERVED
926
Flexible Sensor C High Alarm Action
927
Flexible Sensor C High Alarm Trip
928-929 RESERVED
930
Fuel Sensor C Low Shutdown Enable
931
Fuel Sensor C Low Shutdown Trip
932
Fuel Sensor C Low Shutdown Delay
933
Fuel Sensor C Low Pre-Alarm Enable
934
Fuel Sensor C Low Pre-Alarm Trip
935
Fuel Sensor C Low Pre-Alarm Return
936
Fuel Sensor C Low Pre-Alarm Delay
0 V
937
Fuel Sensor C High Pre-Alarm Enable
On (1), Off (0)
938
Fuel Sensor C High Pre-Alarm Return
0.0 Hz
939
Fuel Sensor C High Pre-Alarm Trip
0.0 Hz
940
Fuel Sensor C High Pre Alarm Delay
On (1), Off (0)
941
RESERVED
0 Hz
942
Fuel Sensor C High Alarm Action
0.0 Hz
943
Fuel Sensor C High Alarm Trip
944
Fuel Sensor C High Alarm Delay
Configuration Parameters – Scheduler (Page 10)
0.0 V
1001
0:00:00
1002
On (1), Off (0)
1003
0.0 V
1004, 1008, 1012, 1016, 1020, 1024, 1028, 1032
1005, 1009, 1013, 1017, 1021, 1025, 1029, 1033
0.0 V
1006, 1010, 1014, 1018, 1022, 1026, 1030, 1034
1007, 1011, 1015, 1019, 1023, 1027, 1031, 1035
0 s
Configuration Parameters – Time (Page 11)
1101
Time of Day
0:00:00
On (1), Off (0)
1102
Day of Week
0 (1=Monday)
1103
Week of Year
1-52
0.0 V
Configuration Parameters – Maintenance Alarms (Page 12)
0 s
On (1), Off (0)
1201
Oil Maintenance Alarm Enable On (1), Off (0)
0.0 V
1202
Oil Maintenance Alarm Action
0 (Action)
Oil Maintenance Alarm Engine
0 s
1203
0 h
Hours
On (1), Off (0)
0.0 V
1204
Air Maintenance Alarm Enable On (1), Off (0)
0 s
1205
Air Maintenance Alarm Action
0 (Action)
0 s
x
Functionality in all DSE4510 & DSE4520 variants.
x
Functionality in all DSE4520 variants.
Mode
x
Functionality in DSE4510 & DSE4520 current sensing variants only
Stop
x
Functionality in DSE4510 & DSE4520 RT & RTH variants only.
Manual
x*
Functionality in DSE4510 & DSE4520 RT & RTH variants only with version 1.6.71 and later.
Auto
0 (Sensor Type)
0 (Pressure Sensor List)
On (1), Off (0)
0 Bar
On (1), Off (0)
0 (Sensor Type)
0 (Temperature Sensor List)
0.00 °C
On (1), Off (0)
Flexible Sensor (1), Fuel Level Sensor (0)
0 (Sensor Type)
0 (Pressure / Temperature / Percentage Sensor List)
0 (Arming)
0 (Action)
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
0 (Action)
0 % / Bar / °C
On (1), Off (0)
0 %
0 s
On (1), Off (0)
0 %
0 %
0 s
On (1), Off (0)
0 %
0 %
0 s
0 (Action)
0 %
0 s
Enable Scheduler
On (1), Off (0)
Schedule Run On or Off Load
On (1), Off (0)
Scheduler Period
Weekly(0), Monthly(1)
Start Time (Entry 1-8)
0:00:00
Day (Entry 1-8)
0 (1=Monday)
Week (Entry 1-8)
1, 2, 3 or 4
Duration (Entry 1-8)
0 s
1104 Day of Month
1-31
1105 Month of Year
1-12
1106 Year
0-99
Air Maintenance Alarm Engine
1206
0 h
Hours
1207 Fuel Maintenance Alarm Enable On (1), Off (0)
1208 Fuel Maintenance Alarm Action 0 (Action)
Fuel Maintenance Alarm Engine
1209
0 h
Hours