Chapter 8 Specifications

8.1 Main unit

Rated operating voltage
Rated frequency
Rated power consumption
Inrush current
Allowable operating
voltage range
Allowable momentary
power-off time
Ambient temperature
Ambient humidity
Breakdown voltage(initial)
Insulation
resistance(initial)
Vibration resistance
Shock resistance
Display method
Power failure
memory method
Size
Weight
note1) Analog input terminals: No.11 to 20 / Pulse input terminal: No.4 and 5
100 to 240V AC
50/60Hz common
8VA
Max. 30A (240VAC at 25℃)
85 to 264V AC (85 to 110% of rated operating voltage)
10ms
-10 to +50℃ (-25 to +70℃ at storage)
30 to 85%RH (at 20℃ non-condensing)
Between the isolated circuits:
2000V for 1min
note) Cut-off current: 10mA
Between the isolated circuits:
100MΩor more
(measured at 500V DC)
10 to 55Hz (1cycle/min) single amplitude : 0.375mm (1h on 3 axes)
2
Min. 294m/s
(5 times on 3 axes)
8-digit, 7-segment LED
EEP-ROM (more than 100,000 overwrite)
48 x 96 x 98.5 mm
approx.265g (without mounting bracket)
45
KW8M Eco-POWER METER (1A/5ACT input type)
A)Outer edge (enclosure)
-All terminals
B)Insulated circuit
・Operating power supply terminals-
Analog input terminals
・Operating power supply terminals-
・RS485-All other terminals
・Pulse output terminals-
Pulse input terminal
All other terminals
note1)