Technology Distance Specifications - HP J9827A Installation Manual

Hp switch zl2 modules
Table of Contents

Advertisement

Technology Distance Specifications

Table 5 Technology Distance Specifications
Technology
100-FX
100-BX
1000-T
10GBASE-T
1000-SX
1000-LX
1000-LH
1000-BX
10-Gig CX4
10-Gig Direct Attach
10-Gig SR
10-Gig LRM
10-Gig LR
10-Gig ER
CX4 Media Converter
1
Cat 6 cabling requires TIA TSB-155A testing for 500 MHz operation and ANEXT.
2
For distances less than 20km, a 10dB attenuator must be used. For distances between 20km and 40km, a 5dB
attenuator must be used. Attenuators can be purchased from most cable vendors.
30
Specifications
Supported cable type
multimode fiber
single mode fiber
twisted-pair copper
twisted-pair copper
multimode fiber
multimode fiber
single mode fiber
single mode fiber
single mode fiber
twinaxial copper
twinaxial copper
multimode fiber
multimode fiber
single mode fiber
single mode fiber
12-strand female-female
multimode fiber MPO ribbon
cable with MTP connectors,
in a crossover (key up/key
up) configuration
Multimode fiber modal
bandwidth
any
N/A
N/A
N/A
160 MHz*km
200 MHz*km
400 MHz*km
500 MHz*km
400 MHz*km
500 MHz*km
N/A
N/A
N/A
N/A
N/A
160 MHz*km
200 MHz*km
400 MHz*km
500 MHz*km
2000 MHz*km
400 MHz*km
500 MHz*km
N/A
N/A
150 MHz*km
500 MHz*km
2000 MHz*km
Supported distances
up to 2,000 meters
0.5 - 10,000 meters
up to 100 meters
Cat 6 unshielded - up to 55
meters
Cat 6 shielded - up to 100
1
meters
Cat 6A unshielded - up to
100 meters
Cat 6A shielded - up to 100
meters
Cat 7 shielded - up to 100
meters
2 - 220 meters
2 - 275 meters
2 - 500 meters
2 - 550 meters
2 - 550 meters
2 - 550 meters
2 - 10,000 meters
2
10 - 70,000 meters
0.5 - 10,000 meters
up to 15 meters
(various lengths offered)
2 - 26 meters
2 - 33 meters
2 - 66 meters
2 - 82 meters
2 - 300 meters
0.5 - 100 meters
0.5 - 220 meters
2 - 10,000 meters
2 - 40,000 meters
1 - 50 meters
1 - 100 meters
1 - 300 meters

Advertisement

Table of Contents
loading