Rigging And Handling - Daikin DPS005 Installation And Maintenance Manual

Rebel commercial packaged rooftop systems
Hide thumbs Also See for DPS005:
Table of Contents

Advertisement

Rigging and Handling

Only trained and qualified personnel should be allowed
to rig loads or operate load rated cranes and/or hoist
assemblies. Do not use a forklift to lift or maneuver the
unit. Failure to use a load rated crane or hoist assembly
to lift or maneuver the unit can cause severe personal
injury and property damage.
Use all lifting points. Improper lifting can cause property
damage, severe personal injury, or death.
Lifting points may not be symmetrical to the center
of gravity of the unit . Ballast or unequal cable lengths
may be required.
Unit is equipped with fork slot reenforcement pieces.
These need to be removed before unit is set on the curb.
Rigging holes for shackles are integral on the unit base. Use
four independent lines, securing one end of a line to a
unit base lifting point and the other end of the line to an
associated spreader bar lifting point .
are examples of instruction labels shipped with each unit.
Use spreader bars to prevent damage to the unit cabinet. Avoid
twisting or uneven lifting of the unit. The cable length from the
bracket to the hook should always be longer than the distance
between the outer lifting points.
If the unit is stored at the construction site for an intermediate
period, take these additional precautions:
1 . Support the unit well along the length of the base rail.
2 . Level the unit (no twists or uneven ground surface).
3 . Provide proper drainage around the unit to prevent
flooding of the equipment.
4 . Provide adequate protection from vandalism, mechanical
contact, etc.
5 . Securely close the doors.
6 . Cover the supply and return air openings.
IM 1125-7 • REBEL ROOFTOPS
WARNING
WARNING
CAUTION
CAUTION
Figure 5
and
Figure 6
Figure 5: Rigging Label 003–015
LIFT ONLY AS SHOWN
USE SPREADER BAR
REMOVE THE FORKLIFT
CHANNELS BEFORE
SETTING THE UNIT ON
THE ROOF CURB
Figure 6: Rigging Label 016–028
LIFT ONLY AS SHOWN
USE SPREADER BAR
10
M
I
eChanICal
nsTallaTIon
www.DaikinApplied.com