• For two standard units which have non-double
deck structure, stacking is not allowed except
for the top equipment with a support structure
for the weight.
• Before putting into operation the equipment
shall be protected from damage and dust
contamination.
• A space shall be remained for the convenience
of inspection and maintenance of the unit. The
minimum maintenance space of the access door
shall be 700mm. For the details of the schematic
diagram of maintenance space→ Fig. 7.
0.5m
Mono and double deck unit
Maintenance
Space
Side by side unit
Fig. 7 Schematic diagram of maintenance space

3.2 Equipment assembly

Use hex bolt for the connection of different
sections of units, and neoprene rubber sealing
strip (2000*20*2.8) should be used at the
connection position.
Adjust the position of the two parts and use hex
bolt M12*80 & hex nut M12 to connect the
basement of unit→ Fig. 9, make sure that unit
will not have relative displacement and be on
the same horizontal plane with height difference
less than 3mm.
Use hex bolt M12*80 & hex nut M12 for the
fixation of the corner of each section→ Fig. 9.
Climate 5000
Space for air duct
Maintenance
Space
Space for air duct
Space for air duct
Maintenance
Space
Space for air duct
Use sealing glue for the connection parts of frame
work and hex flangeself-drilling tapping screws
ST5.5*35 for the fixation of sealing compartment
(8mm PE heat preservation foam stuck in ad-
vance) → Fig. 8-2.
Connect other parts and fasten the bolt.
Notice:
Turn-up of sealing compartment at the
section corner should be placed in
staggered arrangement.If the sealing
compartment is consist of two or more
parts, sealing glue must be used at the
connection part.
Detailed view A
Fig. 8-1 Schematic diagram of section connection 1
Sealing Compartment
PE Heat preservation
cotton 8mm
Neoprene Rubber
seals 2000*20*2.8
Fig. 8-2 Schematic diagram of section connection 2
Al frame
Nylon coner
Plain& split washer
M12
Hex nut M12
Fig. 9 Schematic diagram of base connections
Unit installation | 9
A
B
Detailed view B
Glue
Hex flange self-drilling
tapping screws ST5.5*35
Al frame
Neoprene rubber
seals 2000*20*2.8
Plain washer
M12
Hex bolt M12*80
8736862495(2015/07)