Bosch Climate 5000 Installation, Operation And Maintenance Manual page 18

Modular air handling unit
Hide thumbs Also See for Climate 5000:
Table of Contents

Advertisement

18 | Unit maintenance
Inspection and
No.
maintenance items
7
Sound attenuator
Check the scale, damage and
7.1
corrosion
8
Humidifier
Hight pressure spray
8.1
humidifier
Check the scale in the water
8.1.1
supply tank and humidifier
tank
Check the oil level of the
8.1.2
water pump
8.1.3
Replace the water pump oil
Check the wearing condition
8.1.4
of the coupling
Check the scale in the high
8.1.5
pressure pipe
8.1.6
Check the nozzle
Check the tightness of the
8.1.7
electrical connector
8.2
Wet-film humidifier
Check the scale and damage
8.2.1
on the surface
8.2.2
Check the water supply
Check the tightness of
8.2.3
connections
8.3
Dry steam humidifier
8.3.1
Check the scale and damage
Check the leakage of parts
8.3.2
and joints of the humidifier
Check all parts are properly
8.3.3
working, without abnormal
smell and noise
9
Fan
Check the scale, rust and
9.1
corrosion on the volute casing
Check the vibration, abnormal
9.2
noise and rust of the vane
Tab. 6-2 Inspection and maintenance items 2
8736862495(2015/07)
Maintenance measures
Clean and rectify
Replace if broken
Clean
Clean the nozzle and replace
the organic filter element in it
Tighten if necessary
Clean and rectify
Clean and rectify
Clean and rectify
1
3
6
1
2
M
M
M
Y
Y
Remarks
Inspection and
maintenance
intervals
Only for belt
driven fan
Climate 5000

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mahup(c)-32.40Mahup(c)-06.07

Table of Contents