Air Flow Insufficient; Cooling Capacity Too Small; Leakage - Bosch Climate 5000 Installation, Operation And Maintenance Manual

Modular air handling unit
Hide thumbs Also See for Climate 5000:
Table of Contents

Advertisement

6.4 Air flow insufficient

Air flow insufficient

6.5 Cooling capacity too small

Cold water
Air flow
Coil

6.6 Leakage

Leaking outside
the unit
Water splashing
inside the unit
Tab. 7 Fault analysis and troubleshooting table
Climate 5000
Fault analysis and troubleshooting | 21
Cause
Vane run reversely
Ingress of impurities
Air duct high resistance
The opening of air
valve too small
Fan speed low
Dust
Filter blocked
Coil fin blocked
Cause
Cold water
temperature too high
Cold water flow too low
Low air flow
Coil blocked
Cause
Pipe connection loose
Condensate water
outlet blocked
Unreasonable design
of drain seal
Humidifier abnormal
Steam pressure
abnormal
Low humidification
Remedy
Re-adjust motor wiring
Check and clean
Reduce resistance
Check and adjust
Increase fan speed
Clean
Clean, replace
Clean
Remedy
Adjust cold water temperature
Adjust cold water flow
Increase air flow appropriately
Clean to make it unblocked
Remedy
Tighten
Clean
Adjust hydraulic seal size
Repair in accordance with
the specific reason
Adjust
Increase air supply speed
8736862495(2015/07)