Clock / Printer System Set-Up Menu; Optional 24Vdc 150 Watt Power Supplies - Honeywell HA71 Technical Manual

Digital gas controller
Table of Contents

Advertisement

HA71 Digital Gas Controller

3.1.8 Clock / Printer System Set-Up Menu

Detection of the 10-0229 on the I
System Setup menu item to appear. Selecting it and pressing EDIT
brings up the menu shown below in
entries allow setting of correct local time and date. The ALARM
PRINT ON/OFF entry allows printing to be discontinued if turned to
OFF. PORT allows selection of either RS-232, RS-422 or the parallel
port and only one port may be used at a time. BUFFER DUMP allows
immediate printing of all the 30-35 stored events. PRINT CONFIG
allows immediate printing of all channel variables such as channel
ID's, Engineering Units etc. PRINTER READY / ERROR indicates the
functional status of the printer.
Figure 3-9. Clock/Printer Setup Menu
HA71 Technical Manual
2
C bus causes the Clock/Printer
Figure
3-9. Date / Time menu

3.1.9 Optional 24VDC 150 Watt Power Supplies

The HA71 Controller may be powered from 10-30VDC. However, many
applications require 24VDC power for the monitors or transmitters
providing inputs to the HA71. A 150 watt AC / DC power supply may be
included for these applications (115VAC or 230 VAC selected via slide
switch). When ordered from the factory, it is pre-wired to provide 24VDC
primary power for the HA71 controller as well as any transmitters or
monitors that may be connected by the end user.
SHOCK HAZARD
Risk of electrical shock Disconnect or turn off
power before servicing the equipment
Figure 3-10. 150 Watt 24VDC Power Supply Options
3-10