Quick Step Installation Guide - Midea MSMBAU-09HRDN1-QRD0GW(B) Installation Manual

Mission series inverter air conditioner
Table of Contents

Advertisement

Quick Step Installation Guide

Step 1: Prior to unpacking equipment please inspect boxes for any transport damage to ensure products are in perfect condition.
Step 2: Ensure the equipment model numbers on the boxes correspond with your companies purchase order.
Step 3: Unpack the equipment and ensure all parts are accounted for i.e Indoor / Outdoor & Infra-red Controller.
Step 4: Store the Infra-red service controller safely as this can be used to speed up commissioning and servicing process.
Step 5: Review the installation and maintenance manuals which are provided.
Step 6: Carry out the positioning and installation of indoor and outdoor units as per guidelines within the installation manual.
Step 7: Install refrigerant pipework (Purge with OFN while brazing), electrical wiring & drainage pipe work.
Step 8: Power & Interconnecting control wiring between indoor and outdoor units is made by linking into terminals W-1(L)-2(N)-S-E.
Step 9: Pressure test pipework (Note do not carry out pressure test while connected to outdoor unit to prevent contamination of factory charge)
(1) Strength test in 5 Bar increments up to full test pressure. (2) Then leak test at lower pressure. Evacuate system to 2 torr or lower for appropriate time.
Step 10: If required please add additional refrigerant charge (see table on reverse).
Step 11: Carry out all the commissioning checks required to activate the warranty of the newly installed system.
Step 12: Perform the test operation in accordance with the installation manual to ensure all functions and parts are working correctly.
Step 13: Complete your warranty card document and e-mail this with dated photo of outdoor serial number to:
Note: Installation videos can also be found on the Midea UK YouTube channel.
Please contact your Midea support team if you have any issues during the installation and commissioning process.
Indoor
Outdoor
Model
Model
MSMBAU-09
MOBA02-09
MSMBAU-12
MOBA02-12
MSMBAU-18
MOBA02-18
MSMBAU-24
MOBA02-24
Piping Information
Model:
Liquid Line
Inch
1/4
Gas Line
Inch
3/8
Drain Line
Φ mm
Max Length
M
Max Height
M
Electrical Wiring Information
Model:
Mains Outdoor
Interconnecting/Indoor Power
Power Supply Information
Model:
09
Outdoor
Ph/A
1/16
Indoor
Powered from Outdoor Unit
Mission High Wall Quick Step Installation Guide
Tel: 02074 092009 E-Mail:
Cooling Duty
Heating Duty
(Kw)
(Kw)
3.3
3.75
4.5
4.9
6.2
6.8
8.1
9.3
09
12
18
24
1/4
1/4
3/8
3/8
1/2
5/8
16
16
16
16
25
25
30
50
10
10
20
25
09
12 18
24
3x1.5mm²
3x2.5mm²
5x1.5mm²
5x2.5mm²
12
18
24
1/16
1/16
1/20
technical@fgeuropeuk.co.uk
Outdoor Dimensions
Outdoor Weight
W(mm) D(mm) H(mm)
770
300
555
800
333
554
800
333
554
845
363
702
warranty@fgeuropeuk.co.uk
Indoor Dimensions
(Kg)
W(mm) D(mm) H(mm)
27.1
730
198
29.7
810
200
37.2
980
225
48.5
1090
235
Refrigerant Charging Information
Model:
Pre – Charge
Kg
Charged to
M
Additional
g/m
Refrigerant
Type
Wi Fi Control Available as Standard
12
Indoor
Weight(Kg)
293
7.4
300
8.2
335
10.5
338
12.9
09
12
18
24
0.8
0.95
1.48
2.0
5
5
5
5
15
15
15
30
R410A
Page 33