Setting
S7 program (1)
Channel blocks (1)
OS compilation mode
Plant hierarchy setting (1)
OS project type single station
project (2)
Group display hierarchy (1)
(1) Only applies to MS Basic and MS Standard
2) Only applies to SIMATIC MS PDM
Note
The configuration and the related requirements which must be met are described in detail in
the "Process Control System PCS 7 Maintenance Station"
support.industry.siemens.com/cs/ww/en/view/109485949) manual.
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA
12.1 Configurations with Maintenance Station
Location
SIMATIC Manager
WinCC Explorer
Integrated asset management
Comment
● Message number range
must be the same for all S7
programs in the multiproject/
project
● The name of an S7 program
may not be assigned twice
The channel blocks must be at
least of version V6.1.
Use a corresponding library, if
necessary.
Area-oriented
The settings of the plant hierar‐
chy must be the same in all
projects of the multiproject/
project.
The single station project type
must be selected in project prop‐
erties.
When user diagnostics is used,
the group display hierarchy must
be automatically created.
(https://
297