Siemens SIMATIC PCS 7 Configuration Manual page 255

Process control system compendium part a - configuration guidelines v8.2
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

You proceed in exactly the same way for "TagLogging Slow". You have calculated a mean
value of 100 archive values/s for TagLogging Slow.
● The maximum size for all segments is calculated as follows:
– Where a memory requirement of 16 bytes per measured value is assumed:
– Where a memory requirement of 6 bytes per measured value is assumed:
In our example, we have selected 5 GB.
● The following is calculated for a single segment per day:
– Where a memory requirement of 16 bytes per measured value is assumed:
– Where a memory requirement of 6 bytes per measured value is assumed:
You must then make the following corresponding settings in the "TagLogging Slow"
configuration of the "TagLogging" editor:
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA
approx. 8 GB
(100 archive values/s * 16 bytes/value * 60 s/min * 60 min/h * 24 h/day * 31 days/month
* 2 months)
approx. 3 GB
(100 archive values/s * 6 bytes/value * 60 s/min * 60 min/h * 24 h/day * 31 days/month
* 2 months)
approx. 130 MB
(100 archive values/s * 16 bytes/value * 60 s/min * 60 min/h * 24 h/day * 1 day)
approx. 50 MB
(100 archive values/s * 6 bytes/value * 60 s/min * 60 min/h * 24 h/day * 1 day)
In our example, we have selected 100 MB.
Configuring OS functions
10.4 Archiving
255

Advertisement

Table of Contents
loading

Table of Contents