Engine Controller Description

When a fault circuit is programmed as a SHUTDOWN, the engine will immediately stop when the
fault is activated. A specific shutdown fault can be programmed with a definite time transient
delay period that must expire before the shutdown is activated. The stop sequence will cause the
controllers RUN output to be immediately terminated which will cause the engine to stop.
Fuel Relay
Start Relay
Glow Plug
Relay
Pin #
Title
1
Fuel Relay
2
Crank Relay
3
Glow Plug/At Load
4
Overcrank LED
5
Overspeed LED
6
Oil Pressure LED
7
Water Temperature LED
8
Run LED
9
Lamp Test (input)
10
Manual Mode
11
Auto Mode
12
Ground
13
Magnetic Pickup
14
Oil Pressure
15
Water Temperature
16
Spare (delayed)
17
Spare (Immediate)
18
Relay Power (B+)
4-8 Operation
Figure 4-4 ASM160 Analog Engine Controller Connections
Fuel
1
Crank
2
Glow Plug
3
Overcrank
4
Overspeed
5
Oil Pressure
6
Water Temp.
7
Run
8
Lamp Test
9
Switches shown in OFF position
Table 4-2 ASM160 Terminal Description
Description
Output − Drives a pilot relay to Open/Close the fuel valve.
Output − Drives a pilot relay to Open/Close the Starter Relay to crank engine.
Output − Drives a pilot relay to Open/Close the Glow Plug relay.
Output − On during Overcrank shutdown (engine fails to start after the number of crank cycles).
Output − On during Overspeed shutdown (engine's speed has exceeded the overspeed setpoint).
Output − On during Low Oil Pressure shutdown
Output − On during High Water Temperature shutdown
Output − On during normal engine operation
Input − Closed to ground will turn on all LED outputs.
Input − Closed to B+ will initiate a crank cycle (manual mode)
Input − Closed to B+ will initiate a crank cycle (from a remote source, shorts pins 10 and 11 together).
Ground. Battery (−).
Input − Speed input that monitors engine RPM from engine mounted magnetic pickup. (Delayed for engine start).
Input − Oil Pressure input from sender unit that monitors oil pressure. (Delayed for engine start).
Input − Water Temperature input from sender unit that monitors water temperature. (Delayed for engine start).
Input − Extra input for shutdown fault identification and protection. (Delayed for engine start).
Input − Extra input for shutdown fault identification and protection. (Not delayed for engine start)
Input − Battery Voltage (B+).
10
11
Shielded Twisted Pair Wire
12
13
14
15
16
17
Relay (B+)
18
ON
R1 R2 R3 R4
Glow Plug (ON) or Warm−up/Cooldown (OFF) Mode Select
Crank Attempts
Cooldown Delay (1−300 seconds)
Glow Plug/Warm−up Delay (1−300 seconds)
Crank Disconnect (30−8500Hz)
Overspeed (30−8500Hz)
Auto
Stop
Manual
Remote Start
Magnetic Pickup
Oil Pressure
Water Temperature
Spare (Delayed)
Spare (Immediate)
15A
Starting
Battery (12VDC)
External Components
2
1
Off
Off
On
Off
Off
On
On
On
Crank Attempts
Infinite
10
5
3
MN2416