Analog I/O Modules Calibration
Calibration voltage (ADAM-5017H)
Input Range Code
Module
(Hex)
00h
01h
02h
03h
04h
05h
5017H
06h
07h
08h
09h
0ah
0bh
Table 6-2: Calibration voltage of ADAM-5017H
Note: You can substitute 2.5 V for 20 mA if you remove the current conversion
resistor for that channel. However, the calibration accuracy will be limited
to 0.1% due to the resistor's tolerance.
6-6 ADAM 5000 IO modules User's Manual
Input Range
±10 V
0 ~ 10 V
±5 V
0 ~ 5 V
±2.5 V
0 ~ 2.5 V
±1 V
0 ~ 1 V
±500 mV
0 ~ 500 mV
4 ~ 20 mA
0 ~ 20 mA
Span Calibration Voltage
+10 V
+10 V
+5 V
+5 V
+2.5 V
+2.5 V
+1 V
+1 V
+500 mV
+500 mV
*(1)