BOILER CLEARANCES AND INSTALLATION
The figures indicate the minimum recommended
dimensions for providing easy access around the boiler.
Boiler dimensions are given in mm.
No. of boiler sections
A
mm
No. of boiler sections
A
mm
No. of boiler sections
A
mm
* Clearance for water connections side is 400mm.
This may be either right or left hand side.
For unassembled boiler bodies leave clearance
equal to dimensions a and b for assembly tools
(simplified JD tools for boilers with 8 to 14 sections or
JD-TE tools for boilers with 8 to 20 sections or JD-TE
Plus tools for any other model). Note: not supplied
with the boiler, contact supplier of boiler for the hire of
the same if required.
if a = 500mm ; b = 1600mm
if a = 1600mm ; b = 500mm
Multiple Boiler Installations
A clearance of 200mm must be allowed between
boilers when installed in multiple.
Note
Please note that boilers installed in or close to rooms in which the atmosphere is polluted by chlorine of fluorine compounds may
be subject to high corrosion.
For example: hairdressing salons, industrial premises (solvents), cooling equipment, etc.
Boilers installed in such locations will not be covered by the guarantee.
Concord ESi -
Installation and Servicing
8
9
10
11
970
1058
1146
1234
12
14
16
18
1322 1498
1674
1850
20
2026
GENERAL
1406
The combustion air
must reach the burner
from the front
CON 2 7
11