Operation; Settable Functions - Honeywell TWM 9000 Supplementary Instructions Manual

Signal converter for electromagnetic flowmeters
Hide thumbs Also See for TWM 9000:
Table of Contents

Advertisement

TWM 9000

4.1 Settable functions

• For Foundation Fieldbus the totalizers of the signal converter are not available!
• The following tables describe only the menus, functions and parameters that are different
between the standard signal converter and the Foundation Fieldbus signal converter.
• For the electrical connections of the outputs, inputs and all settings of functions that are not
listed in the following tables refer to the standard product documentation.
No.
Displayed text
A quick setup
A2
Tag
B test
B3.5
Foundation fieldbus
C setup
C1.2.3
time constant
C5.1.1
Tag
C3
Totalizer
C4
I/O HART
C5.4
2. meas. page
C5.4.1
measurement 1.line
C5.4.2
format 1.line
C5.4.3
measurement 2.line
C5.4.4
format 2.line
C5.4.5
measurement 3.line
C5.4.6
format 3.line
C5.8
Foundation Field
C5.8.1
Simulate
C5.8.2
Information
34-VF-25-37 iss.2 GLO Jan 18 US
Description and settings
Identifier for the measurement in a plant, appears in the display header
(maximum 8 digits).
Note: Only read, not changeable!
Display information about Foundation fieldbus interface.
For all flow measurements and outputs.
xxx.x s; range: 0.0...100 s
Note: Only read, not changeable!
Identifier for the measurement in a plant, appears in the display header
(maximum 8 digits).
Note: Only read, not changeable!
Not available for Foundation Fieldbus devices!
Not available for Foundation Fieldbus devices!
In case of Foundation Fieldbus device, the second measurement page is
meant to check the output values of the different function blocks. Only
Foundation Fieldbus values can be selected here. The analogue inputs are
shown with exactly the value, seen on the bus system.
Select: AI1 analog inp. / AI2 analog inp. / AI3 analog inp. / PID / INT1
integrator / INT2 integrator /
Fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space.
Select: AI1 analog inp. / AI2 analog inp. / AI3 analog inp. / PID / INT1
integrator / INT2 integrator /
Fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space.
Select: AI1 analog inp. / AI2 analog inp. / AI3 analog inp. / PID / INT1
integrator / INT2 integrator /
Fixed number of digits after the decimal point or automatic, where the
number of digits is automatically adjusted to the available space.
-
Select: disabled / enabled
Display information about hardware and software versions, the calibration
and test date of this interface.
www.honeywellprocess.com

OPERATION

4
11