Inverter Status Monitor Read Only - Toshiba Tosvert-130 Installation Manual

Transistor inverter vector drive series
Table of Contents

Advertisement

8.2 Inverter Status Monitor Read Only

Registers
bit
05
word
Output frequency Monitor
06
0
Run • stop status
1
Run enable
2
Forward • reverse status
3
Acc/dec #1 / #2 selection status
4
Reserved
5
Gate Block Status
6
Reserved
7
Jog mode status
8
Feedback enable status
9
Compulsory DC injection braking
mode
A
Fundamental parameter switching
B
coast stop command status
C
Emergency off command
D
Reserved
E
Main Circuit Undervoltage (MSV)
F
Reserved
07
word
Output current Monitor
08
word
Output voltage Monitor
09
word
Reserved
0A
word
Reserved
Function
Bank
DPRAM
DPRAM
DPRAM
DPRAM
15
Address
Adjustment Range
0000
0.00~400.00Hz
0002
0: Stopped
1: Running
0: Run enabled
1: Stopped
0: Reverse
1: Forward
0: Acc / dec #1
1: Acc / dec #2
Always "0"
0:gate block active
1:gate block inactive
Always "0"
0: Normal (acc/dec
mode)
1: Jog mode
0: Feedback valid
1: Feedback invalid
0: DC braking inactive
1: DC braking active
0: V/F #1
1: V/F #2
0: Normal
1: coast to stop
0: normal
1: Emergency off
Always "0"
0:normal
1:MSV
Always "0"
0004
0~255%
0006
0~232%
Multiplier
0.01