Samsung AM***XMDCH Series Installation Manual page 43

Table of Contents

Advertisement

❋ Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB since it is
charged with high DC voltage.
❋ When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
❋ When there were error, 'Discharge mode of DC link voltage' may not have been effective. Especially if error E464 has
been occurred, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link
voltage' .
❋ During "Discharge mode of DC link voltage", voltage of INV will be displayed.
K3(Number of press)
1 time
K4(Number
KEY operation
of press)
1 time
Outdoor unit model
2 times
Order frequency of compressor
3 times
4 times
Discharge temperature of compres-
5 times
6 times
IPM temperature of compressor
7 times
CT sensor value of compressor
8 times
Suction temperature
9 times
COND OUT temperature
10 times
Liquid pipe temperature
11 times
TOP temperature of compressor
12 times
Outdoor temperature
13 times
EVI inlet temperature
14 times
EVI outlet temperature
15 times
Main EEV step
16 times
17 times
18 times
Current frequency of compressor
Master indoor unit address
19 times
(Master indoor unit can be selected
by wired remote-controller)
KEY operation
Initialize (Reset) setting
High pressure
Low pressure
sor
EVI EEV step
Fan step
Display on segment
SEG 1
7HP(AM060 XM )
1
2
3
4
188.6
5
188.6
6
7
-43.6
8
-43.6
9
-43.6
A
188.6
B
-43.6
C
-43.6
D
-43.6
E
F
G
H
I
Master indoor unit not selected
J
If indoor unit No.1 is selected as the master unit
Display on segment
Same as initial state
SEG2, 3, 4
0, 0, 7
120 Hz
1,2,0
1.52 MPa
1, 5, 2
0.43 MPa
0, 4, 3
°
°
C)
F(87
0, 8, 7
°
°
F(87
C)
0, 8, 7
2 A
0, 2, 0
°
°
F(-42
C)
-, 4, 2
°
°
F(-42
C)
-, 4, 2
°
°
F(-42
C)
-, 4, 2
°
°
F(87
C)
0, 8, 7
°
°
C)
F(-42
-, 4, 2
°
°
F(-42
C)
-, 4, 2
°
°
F(-42
C)
-, 4, 2
2000 steps
2, 0, 0
300 steps
3, 0, 0
13 steps
0, 1, 3
120 Hz
1,2,0
BLANK , N , D
0 , 0 , 1
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am060mxmdch series

Table of Contents