Samsung AM***XMDCH Series Installation Manual page 16

Table of Contents

Advertisement

Refrigerant pipe installation
Tightening flare connection area
Check that the flaring is properly made.
Align the center of the piping and sufficiently tighten the flare nut with fingers. Finally, tighten the flare nut with torque
wrench until the wrench clicks. When tightening the flare nut with torque wrench, ensure the direction for tightening
follows the arrow on the wrench.
Make sure to use ester oil to coat the flare connection section.
Flare connection section
Outer diameter
[D, mm (inch)]
Ø6.35 (1/4)
Ø9.52 (3/8)
Ø12.70 (1/2)
Ø15.88 (5/8)
Blowing Nitrogen gas should be done when brazing the pipe.
Make sure to use the provided flare nut.
CAUTION
Make sure that there are no cracks on the bent pipe.
Do not fasten the flare nut with excessive strength.
Use ester oil to coat the flare connection area to prevent refrigerant leak. R410A is a high pressure refrigerant.
Therefore, there is a risk of refrigerant leakage if the flare connection is not coated with ester oil.
16
Pipe
Flare nut
Connection torque
140~180
14~18
350~430
34~42
500~620
49~61
690~830
68~82
Flare dimension
[L, mm (inch)]
8.70~9.10(0.343~0.358)
12.80~13.20(0.504~0.520)
16.20~16.60(0.638~0.654)
19.30~19.70(0.760~0.776)
Flare shape [mm (inch)]
R 0.4~0.8
(0.016~0.032)
D
L