Classification
Maximum
Outdoor unit
allowable
~ Indoor
length of
units
pipe
Maximum
Outdoor unit
allowable
~ Indoor
height
units
Maximum allowable length
after Y-joint
EEV Kit
EEV Kit ~
Actual pipe lengh
Indoor units
❋ When the equivalent length between an outdoor unit and the farthest indoor unit exceeds 90m (295'), upgrade the low
pressure pipe of the main pipe one step.
❋ Note 1) When indoor unit is located at higher level than outdoor unit, allowable height difference is 40m(131ft), but
when the indoor unit is located at lower level than outdoor unit, allowable height difference is 50m(164ft).
Y-joint connection
The distance between the outdoor unit and the farthest indoor unit ≤ 150m (492')
Actual
Ex) 8 indoor units
Length
a+b+c+d+e+f+g+p≤ 150m (492')
Equivalent
The distance between an outdoor unit and the farthest indoor unit ≤ 175m (574')
length
Main pipe
The main pipe(a) from the outdoor unit to the first Y-joint should be less than 110m
length
(361').
Total
The sum of the total length of pipes should be less then 300m (984').
length
H1: The difference of height between an outdoor unit and indoor unit < 50/40m
Height
Note 1)
(164'/131')
Height
H2: The difference of height between indoor units ≤ 15m (49')
The distance between the first Y-joint and
the farthest indoor unit ≤ 40m (131')
Actual
Length
Ex) 8 indoor units
b+c+d+e+f+g+p≤ 40m (131')
2m (6.6') or less
20m (66') or less
Ex) 6 indoor units
a+b+c+d+j ≤ 150m (492')
Allowable length between EEV kit and
an indoor unit ≤ 20m (65')
Ex) h, l, j ≤ 20m (65')
Model name
MEV-E24SA
1 indoor
MEV-E32SA
MXD-E24K132A
MXD-E24K200A
2 indoor
MXD-E32K200A
MXD-E24K232A
MXD-E24K300A
3 indoor
MXD-E32K224A
MXD-E32K300A
Y-joint / EEV kit connection
Remarks
Apply to products
without EEV (Wall
mounted & ceiling)
19