Samsung AM***XMDCH Series Installation Manual page 41

Table of Contents

Advertisement

Optional item
Input unit
Oil collection
Main
interval
Temperature to
trigger defrost
Main
operation
Fan speed
correction for
Main
outdoor unit
Silent mode for
Main
night-time
High-head
Main
condition setting
Long-pipng
condition setting
(Setting is
Main
unnecessary
if high-head
condition is set)
Energy saving
Main
setting
Not applicable
Main
Not applicable
Main
Channel address
Main
Snow
accumulation
Main
prevention
control
Silent mode for
Main
external contact
SEG1
SEG2 SEG3 SEG4
0
0
0
4
0
1
0
0
0
5
0
1
0
0
0
6
0
1
0
0
0
1
0
7
0
2
0
3
0
0
0
1
0
8
0
2
0
3
0
0
0
1
0
9
0
2
0
0
1
0
0
1
0
0
1
1
0
1
0
0
1
2
0
1
A
U
1
3
0 - 15
0
0
1
4
0
1
0
0
0
1
1
5
0
2
0
3
Function of the option
Factory default
Shorten the interval by 1/2
Factory default
Apply setting when the product is
being installed in humid area such
as near river or lake
Factory default
Increase fan speed
Disabled (Factory default)
LEVEL 1
LEVEL 2
LEVEL 3
Disabled (Factory default)
Level 1 of height difference type 1
(indoor unit is lower than outdoor unit)
Not applicable
Height difference type 2 (outdoor unit
is lower than indoor unit)
Disabled (Factory Default)
LEVEL 1
Not applicable
Disabled (Factory default)
Enabled
Not applicable
Not applicable
Not applicable
Not applicable
Automatic setting
(factory default)
Manual setting for channel
0 – 15
Enabled
Disabled (Factory default)
-
LEVEL 1
LEVEL 2
LEVEL 3
Remarks
The defrost option shortens
the starting time of the defrost
operation
Increase the outdoor unit's fan
speed to maximum value
Enables the silent mode for
night-time in cooling mode.
(It operates automatically
depending on the temperature.)
When outdoor unit is located
40~80m above the indoor unit
When indoor unit is over 30m
above the outdoor unit
When equivalent length of farthest
indoor unit from the outdoor unit is
over 100m
Energy saving mode triggers
when the room temperature
reaches desired temperature
while operating in heating mode.
Address for classifying the product
from upper level controller(DMS,S-
NET 3,etc.)
During snow accumulation , the fan
may spin even when the unit is not
in operation
If the external contact interface
module (MIM-B14) is used, entering
the silent mode is available with
contact signal in cooling and
heating mode.
41