Insulating refrigerant pipe
You must insulate refrigerant pipe, Y-joint, header joint, and pipe connection area.
If you insulate the pipes, the condensed water does not fall from the pipes.
Check if there are any insulation cracks on the bent pipe.
Insulation
Gas side pipe
Liquid side pipe
Pipe insulation
The insulation of the gas and liquid pipes can be in
contact with each other but they should not press
excessively against each other.
When contacting the gas side and liquid side pipe, use
thicker insulation.
Insulation
Gas pipe
Install the insulation not to be get wider and use adhesive on the connection part of it to prevent moisture
entering.
CAUTION
Bind the refrigerant pipe with insulation tape if it is exposed to outside sunlight. (When binding the pipe with
finishing tape, be careful not to reduce the thickness of the insulation.)
Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.
When the thickness of insulation is reduced, supplement the reduced thickness with additional insulation.
Additional
insulation
Clamp
Indoor unit
Indoor
unit
Insulation
Liquid pipe
Hanger
Insulation for
a
refrigerant pipe
a x 3
Insulation
Install the insulation to be
overlapped
Fix securely without any gap.
Pipe insulation after insulating EEV kit
When installing the gas side and liquid side pipes, leave
10mm (3/8 inch) of space.
When contacting the gas side and liquid side pipe, use
thicker insulation.
10mm (3/8")
10mm (3/8")
Gas pipe
10mm (3/8")
Liquid pipe