Replacing A Spa 300 Series Relay By A 615 Series Ied - ABB Relion 615 series Installation Manual

Hide thumbs Also See for Relion 615 series:
Table of Contents

Advertisement

1MRS756375 K
4.3.15
615 series
Installation Manual

Replacing a SPA 300 series relay by a 615 series IED

1.
Make a new panel cut-out to the existing mounting panel according to the
dimensional drawing.
B
GUID-F20D587E-5E99-4593-B9EE-A1B125A95524 V1 EN
Figure 36:
New panel cut-out and screw hole dimensions for replacing a
SPA 300 series relay
A Min. 186 mm
B 161.5 ± 1 mm
C 224 mm
D 176 mm
E 7 mm
2.
Drill new screw holes (∅4.5 mm) to the panel according to the dimensional
drawing.
3.
Mount the installation plate to the panel cut-out with M5 thread forming screws.
A
C
Section 4
Mounting
D
E
49